If the servo motor is used to control a vertical axis, the machine movable part can have a
slight shift when the holding brake becomes open or closed. To eliminate such slight shift,
you can configure a delay time for the close or open time of the motor holding brake by
setting the parameters p1216 and p1217.
Note
The default values of p1216 and p1217 depend on the rated power of the motor which
connects to the servo drive.
Note
For 200 V variant servo drives, the actual motor holding brake time consists of the time delay
of the motor brake and the time delay of the current amplifying component (a relay in the
example above); therefore, you can set the values of p1216 and p1217 as follows:
p1216 = motor brake opening time + relay opening time
p1217 = motor brake closing time + relay closing time
NOTICE
Shortening the service life of motor brake
The motor brake is used for holding purpose only. Frequent emergency stops with the
motor brake will shorten its service life.
Unless absolutely necessary, do not apply the motor brake as an emergency stop or
deceleration mechanism.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002
Connecting
4.7 Motor holding brake