Fault
F1912: PROFIdrive: Clock
cycle synchronous operation
sign-of-life failure
Message class: Communica-
tion error to the higher-level
control system (9)
Reaction: OFF1
Acknowledgement:
IMMEDIATELY
F7011: Motor overtempera-
ture
Message class: Motor over-
load (8)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F7085: Open-loop/closed-
loop control parameters
changed
Message class: Error in the
parameterization / configura-
tion / commissioning proce-
dure (18)
Reaction: NONE
Acknowledgement:
IMMEDIATELY
F7090: Drive: Upper torque
limit less than the lower
torque limit
Message class: Error in the
parameterization / configura-
tion / commissioning proce-
dure (18)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002
Cause
The maximum permissible number of er-
rors in the controller sign-of-life (clock
synchronous operation) has been exceed-
ed in cyclic operation.
Motor overloaded
Motor surrounding temperature too
high
Wire breakage or sensor not connected
Motor temperature model incorrectly
parameterized
Open-loop/closed-loop control parameters
have had to be changed for the following
reasons:
As a result of other parameters, they
have exceeded the dynamic limits.
They cannot be used due to the fact
that the hardware detected not having
certain features.
The upper torque limit is lower than the
lower torque limit.
12.2 List of faults and alarms
Remedy
Physically check the bus (cables, con-
nectors, terminating resistor, shielding,
etc).
Correct the interconnection of the control-
ler sign-of-life.
Check whether the controller correctly
sends the sign-of-life (e.g. create a trace
with STW2.12...STW2.15 and trigger sig-
nal ZSW1.3).
Check the permissible telegram failure
rate (p0925).
Check the bus and controller for utilization
level (e.g. bus cycle time was set too
short).
Reduce the motor load.
Check the surrounding temperature and
the motor ventilation.
Check the wiring and the connection.
Check the motor temperature model pa-
rameters.
It is not necessary to change the parameters
as they have already been correctly limited.
The upper torque limit (p29050) must be ≥
lower torque limit (p29051)
Diagnostics