Alarm
A7463: EPOS: External block
change not requested in the
traversing block
Message class: Application /
technological function faulted
(17)
A7468: EPOS: Traversing
block jump destination does
not exist
Message class: Error in the
parameterization / configura-
tion / commissioning proce-
dure (18)
A7469: EPOS: Traversing
block < target position < soft-
ware limit switch minus
Message class: Error in the
parameterization / configura-
tion / commissioning proce-
dure (18)
A7470: EPOS: Traversing
block > target position > soft-
ware limit switch plus
Message class: Error in the
parameterization / configura-
tion / commissioning proce-
dure (18)
A7471: EPOS: Traversing
block target position outside
the modulo range
Message class: Application /
technological function faulted
(17)
A7472: EPOS: Traversing
block ABS_POS/ABS_NEG
not possible
Message class: Application /
technological function faulted
(17)
A7473: EPOS: Beginning of
traversing range reached
Message class: Application /
technological function faulted
(17)
A7474: EPOS: End of trav-
ersing range reached
Message class: Application /
technological function faulted
(17)
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002
Cause
For a traversing block with the block
change enable
CONTINUE_EXTERNAL_ALARM, the
external block change was not requested.
Alarm value (r2124, interpret decimal):
Number of the traversing block.
In a traversing block, a jump was pro-
grammed to a non-existent block.
Alarm value (r2124, interpret decimal):
Number of the traversing block with a jump
destination that does not exist.
In the traversing block the specified abso-
lute target position lies outside the range
limited by the software limit switch minus.
In the traversing block the specified abso-
lute target position lies outside the range
limited by the software limit switch plus.
In the traversing block the target position
lies outside the modulo range.
In the traversing block the positioning
mode ABS_POS or ABS_NEG were pa-
rameterized with the modulo correction not
activated.
When traversing, the axis has moved to
the traversing range limit.
When traversing, the axis has moved to
the traversing range limit.
12.2 List of faults and alarms
Remedy
Resolve the reason as to why the edge is
missing at STW1.13.
Correct the traversing block.
Add the missing traversing block.
Correct the traversing block.
Change software limit switch minus
(p2580).
Correct the traversing block.
Change software limit switch plus (p2581).
In the traversing block, correct the target
position.
Change the modulo range (p29246).
Correct the traversing block.
Move away in the positive direction.
Move away in the negative direction.
Diagnostics
277