Advertisement

Note
STW1.10 must be set to 1 to allow the PLC to control the drive.
Control words when telegrams 7, 9, and 110 are used
● Control word SATZANW
Control words when telegram 9 is used
● Control word MDI_MOD
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002
Signal
Description
SATZANW.0
1 = Traversing block selection, bit 0
SATZANW.1
1 = Traversing block selection, bit 1
SATZANW.2
1 = Traversing block selection, bit 2
SATZANW.3
1 = Traversing block selection, bit 3
SATZANW.4
1 = Traversing block selection, bit 4
SATZANW.5
1 = Traversing block selection, bit 5
SATZANW.6
Reserved
SATZANW.7
Reserved
SATZANW.8
Reserved
SATZANW.9
Reserved
SATZANW.10 Reserved
SATZANW.11 Reserved
SATZANW.12 Reserved
SATZANW.13 Reserved
SATZANW.14 Reserved
SATZANW.15 1 = Activate MDI
0 = Deactivate MDI
Signal
Description
MDI_MOD.0
1 = Absolute positioning is selected
0 = Relative positioning is selected
MDI_MOD.1
0 = Absolute positioning through the shortest distance
1 = Absolute positioning in the positive direction
MDI_MOD.2
2 = Absolute positioning in the negative direction
3 = Absolute positioning through the shortest distance
MDI_MOD.3
Reserved
MDI_MOD.4
Reserved
MDI_MOD.5
Reserved
MDI_MOD.6
Reserved
MDI_MOD.7
Reserved
MDI_MOD.8
Reserved
MDI_MOD.9
Reserved
MDI_MOD.10
Reserved
MDI_MOD.11
Reserved
MDI_MOD.12
Reserved
MDI_MOD.13
Reserved
MDI_MOD.14
Reserved
MDI_MOD.15
Reserved
PROFINET communication
8.3 Control word STW and status word ZSW
167