Diagnostics
12.2 List of faults and alarms
Fault
F30021: Ground fault
Message class: Ground fault /
inter-phase short-circuit de-
tected (7)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30027: Precharging DC link
time monitoring
Message class: Infeed faulted
(13)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30036: Internal overtemper-
ature
Message class: Power elec-
tronics faulted (5)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30050: 24 V supply over-
voltage
Message class: Supply volt-
age fault (undervoltage) (3)
Reaction: OFF2
Acknowledgement: POWER
ON
270
Cause
Power unit has detected a ground fault.
Ground fault in the power cables.
Winding fault or ground fault at the
motor.
The power unit DC link was not able to
be pre-charged within the expected
time.
There is no line supply voltage con-
nected.
The line contactor/line side switch has
not been closed.
The line supply voltage is too low.
The pre-charging resistors are over-
heated as there were too many pre-
charging operations per time unit
The pre-charging resistors are over-
heated as the DC link capacitance is
too high.
The pre-charging resistors are over-
heated.
The pre-charging resistors are over-
heated as the line contactor was closed
during the DC link fast discharge
through the Braking Module.
The DC link has either a ground fault or
a short-circuit.
The pre-charging circuit is possibly
defective.
The temperature inside the drive converter
has exceeded the permissible temperature
limit.
Insufficient cooling, fan failure.
Overload.
Surrounding temperature too high.
The voltage monitor signals an overvoltage
fault on the module.
Remedy
Check the power cable connections.
Check the motor.
Check the line supply voltage at the input
terminals.
Check whether the fan is running.
Check the fan elements.
Check whether the surrounding tempera-
ture is in the permissible range.
Notice:
This fault can only be acknowledged once the
permissible temperature limit minus 5 K has
been fallen below.
Check the 24 V power supply.
Replace the module if necessary.
SINAMICS V90, SIMOTICS S-1FL6