Alarm
A1940: PROFIdrive: clock
cycle synchronism not
reached
Message class: Communica-
tion error to the higher-level
control system (9)
A1944: PROFIdrive: Sign-of-
life synchronism not reached
Message class: Communica-
tion error to the higher-level
control system (9)
A5000: Drive heat sink over-
temperature
Message class: Power elec-
tronics faulted (5)
A7012: Motor temperature
model 1/3 overtemperature
Message class: Motor over-
load (8)
A7441: LR: Save the position
offset of the absolute encoder
adjustment
Message class: Application /
technological function faulted
(17)
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002
Cause
The bus is in the data exchange state and
clock synchronous operation has been
selected using the parameterizing tele-
gram. It was not possible to synchronize to
the clock cycle specified by the master.
The master does not send a clock
synchronous global control telegram
although clock synchronous operation
was selected when configuring the bus.
The master is using another clock
synchronous DP clock cycle than was
transferred to the slave in the parame-
terizing telegram.
At least one drive object has a pulse
enable (not controlled from PROFIdrive
either).
The bus is in the data exchange state and
clock synchronous operation has been
selected using the parameterizing tele-
gram.
Synchronization with the master sign-of-life
(STW2.12...STW2.15) could not be com-
pleted because the sign-of-life is changing
differently to how it was configured in the
Tmapc time grid.
The alarm threshold for overtemperature at
the inverter heat sink has been reached.
If the temperature of the heat sink increas-
es by an additional 5 K, then fault F30004
is initiated.
The motor temperature model 1/3 identi-
fied that the alarm threshold was exceed-
ed.
The status of the absolute encoder ad-
justment has changed.
In order to permanently save the deter-
mined position offset (p2525), it must be
saved in a non-volatile fashion (p0977).
12.2 List of faults and alarms
Remedy
Check the master application and bus
configuration.
Check the consistency between the clock
cycle input when configuring the slave
and clock cycle setting at the master.
Check that no drive object has a pulse
enable. Only enable the pulses after syn-
chronizing the PROFIdrive.
Ensure that the master correctly increments
the sign-of-life in the master application clock
cycle Tmapc.
Check the following:
Is the surrounding temperature within the
defined limit values?
Have the load conditions and the load
duty cycle been appropriately dimen-
sioned?
Has the cooling failed?
Check the motor load and reduce it if
required.
Check the motor surrounding tempera-
ture.
Not necessary.
This alarm automatically disappears after the
offset has been saved.
See also: p2525 (LR encoder adjustment
offset)
Diagnostics
275