Diagnostics
12.2 List of faults and alarms
Fault
F7475: EPOS: Target posi-
tion < start of traversing
range
Message class: Error in the
parameterization / configura-
tion / commissioning proce-
dure (18)
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
F7476: EPOS: Target posi-
tion > end of the traversing
range
Message class: Error in the
parameterization / configura-
tion / commissioning proce-
dure (18)
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
F7481: EPOS: Axis position <
software limit switch minus
Message class: Application /
technological function faulted
(17)
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
F7482: EPOS: Axis position >
software limit switch plus
Message class: Application /
technological function faulted
(17)
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
F7484: EPOS: Fixed stop
outside the monitoring win-
dow
Message class: Application /
technological function faulted
(17)
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
264
Cause
The target position for relative traversing
lies outside the traversing range.
The target position for relative traversing
lies outside the traversing range.
The actual position of the axis is less than
the position of the software limit switch
minus.
The actual position of the axis is greater
than the position of the software limit
switch plus.
In the "fixed stop reached" state, the axis
has moved outside the defined monitoring
window (p2635).
Remedy
Correct the target position.
Correct the target position.
Correct the target position.
Change software limit switch minus (CI:
p2580).
See also: p2580 (EPOS software limit switch
minus), p2582 (EPOS software limit switch
activation)
Correct the target position.
Change software limit switch plus (CI:
p2581).
See also: p2580 (EPOS software limit switch
minus), p2582 (EPOS software limit switch
activation)
Check the monitoring window (p2635).
Check the mechanical system.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002