Mounting

3.1

Mounting the drive

Protection against the spread of fire
The inverter may be operated only in closed housings or in higher-level control cabinets with
protective covers that are closed, and when all of the protective devices are used. The
installation of the inverter in a metal control cabinet or the protection with another equivalent
measure must prevent the spread of fire and emissions outside the control cabinet.
Protection against condensation or electrically conductive contamination
Protect the inverter, e.g. by installing it in a control cabinet with degree of protection IP54
according to IEC 60529 or NEMA 12. Further measures may be necessary for particularly
critical operating conditions.
If condensation or conductive pollution can be excluded at the installation site, a lower
degree of control cabinet protection may be permitted.
Death or severe personal injury from harsh installation environment
A harsh installation environment will jeopardize personal safety and equipment. Therefore,
• Do not install the drive and the motor in an area subject to inflammables or
• Do not install the drive and the motor in an area where it is likely to be exposed to
• Do not keep the drive exposed to strong electro-magnetic interference.
Hot surface
During operation and for a short time after switching-off the drive, the surfaces of the drive
can reach a high temperature. Avoid coming into direct contact with the drive surface.
For mounting conditions, see Technical data - servo drives (Page 38).
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002
WARNING
combustibles, water or corrosion hazards.
constant vibrations or physical shocks.
CAUTION
3
53