Control functions
7.2 Basic positioner (EPOS)
The whole process is shown in the diagram below:
Follow the steps below to perform referencing with this mode:
1. Set relevant parameters:
2. Set STW1.11 (0→1) to start referencing.
Note
During the referencing, if STW1.11 is set to 0, the referencing stops.
142
Parameter
Range
p2599
-2147482648 to
2147482647
p2600
-2147482648 to
2147482647
p2604
0 to 1
p2608
1 to 40000000
p2609
0 to 2147482647
p2611
1 to 40000000
Factory
Unit
setting
0
LU
Sets the position value for the refer-
ence point coordinate.
0
LU
Reference point offset
0
-
Sets signal source for start direction
of searching cam:
300
1000
Speed for searching zero mark
LU/min
20000
LU
Maximum distance for searching the
zero mark
300
1000
Speed for searching reference point
LU/min
Operating Instructions, 09/2016, A5E37208830-002
Description
0: start in positive direction
1: start in negative direction
SINAMICS V90, SIMOTICS S-1FL6