Siemens SIMOTICS S-1FL6 Operating Instructions Manual page 236

Sinamics / simotics
Hide thumbs Also See for SIMOTICS S-1FL6:
Table of Contents

Advertisement

Parameters
11.2 Parameter list
Par. No.
Name
p29023
Tuning: One-button auto
tuning configuration
Description: One-button auto tuning configuration.
Bit 0: The speed controller gain is determined and set using a noise signal.
Bit 1: Possible required current setpoint filters are determined and set using a noise signal. As a conse-
quence, a higher dynamic performance can be achieved in the speed control loop.
Bit 2: The inertia moment ratio (p29022) can be measured after this function is running. If not set, the iner-
tia moment ratio must be set manually with p29022.
Bit 7: With this bit set, multi-axes are adapted to the dynamic response set in p29028. This is necessary
for interpolating axes. The time in p29028 should be set according to the axis with the lowest dynamic re-
sponse.
p29024
Tuning: Real-time auto
tuning configuration
Description: Real-time auto tuning configuration.
Bit 2: The inertia moment ratio (p29022) is estimated while the motor is running, if not set, the inertia mo-
ment ratio must be set manually with p29022.
Bit 3: If not set, the inertia moment ratio (p29022) is estimated only once and the inertia estimator is deac-
tivated automatically after the estimation is completed. If the bit is set to 1, the inertia moment ratio is esti-
mated in real time and the controller adapts the parameters continuously. You are recommended to save
the parameters when the estimation result is satisfied. After that, when you power on the drive next time,
the controller will be started with the optimized parameters.
Bit 6: The adaption of current setpoint filter. This adaption may be necessary if a mechanical resonance
frequency changes in operation. It can also be used to dampen a fixed resonance frequency. Once the
control loop has stabilized, this bit should be deactivated and to save parameters in a non-volatile
memory.
Bit 7: With this bit set, multi-axes are adapted to the dynamic response set in p29028. This is necessary
for interpolating axes. The time in p29028 should be set according to the axis with the lowest dynamic re-
sponse.
p29025
Tuning: Configuration
overall
Description: Overall configuration of auto tuning, apply for both one-button and real-time auto tuning.
Bit 0: For significant differences between the motor and load moment of inertia, or for low dynamic perfor-
mance of the controller, then the P controller becomes a PD controller in the position control loop. As a
consequence, the dynamic performance of the position controller is increased. This function should only
be set when the speed pre-control (bit 3 = 1) or the torque pre-control (bit 4 = 1) is active.
Bit 1: At low speeds, the controller gain factors are automatically reduced in order to avoid noise and oscil-
lation at standstill. This setting is recommended for incremental encoders.
Bit 2: The estimated load moment of inertia is taken into account for the speed controller gain.
Bit 3: Activates the speed pre-control for the position controller.
Bit 4: Activates the torque pre-control for the position controller.
Bit 5: Adapts acceleration limit.
p29026
Tuning: Test signal dura-
tion
Description: The duration time of the one-button auto tuning test signal.
236
Min
Max
-
-
-
-
-
-
0
5000
Factory
Unit
Data
Setting
type
0x0007
-
U16
0x004c
-
U16
0x0004
-
U16
2000
ms
U32
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002
Effective
Can be
changed
IM
T
IM
T
IM
T
IM
T

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics v90

Table of Contents