Torque Setpoint; Torque Control With External Analog Torque Setpoint - Siemens SINAMICS V90 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

Control functions
7.6 Torque control (T)
● With load
7.6.2

Torque setpoint

Two sources are available for torque setpoint:
● External setpoint: analog input 2
● Fixed setpoint: p29043
These two resources can be selected with the digital input signal TSET:
Signal
Level
TSET
0 (default)
Refer to "DIs (Page 70)" for detailed information about the signal TSET.
7.6.2.1

Torque control with external analog torque setpoint

In the T mode, when the digital input signal TSET is at low level, analog voltage from the
analog input 2 is used as the torque setpoint.
The analog voltage from the analog input 2 corresponds to a parameterized torque value
scaling (p29041[0]). If p29041[0] = 100%, analog input voltage of 10 V corresponds to rated
torque; if p29041[0] = 50%, the analog input value of 10 V corresponds to 50% of the rated
torque.
Parameter
Range
p29041[0]
0 to 100
Note
The value of analog input 2 can be monitored through parameter p29351.
180
Analog torque setpoint (analog input 2)
1
Fixed torque setpoint (p29043)
Factory setting
100
Source of torque setpoint
Unit
%
Scaling for analog torque setpoint (corresponding to 10
V)
Operating Instructions, 07/2015, 6SL3298-0AV60-0BP0
Description
SINAMICS V90, SIMOTICS S-1FL6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics s-1fl6

Table of Contents