Par. No.
Name
p1656 *
Activates current setpoint
filter
Description: Setting for activating/de-activating the current setpoint filter.
Dependency: The individual current setpoint filters are parameterized as of p1658.
Note: If not all of the filters are required, then the filters should be used consecutively starting from filter 1. The
drive unit displays the value in hex format. To know the logic (high/low) assignment to each bit, you must
convert the hex number to the binary number, for example, FF (hex) = 11111111 (bin).
p1658 *
Current setpoint filter 1
denominator natural fre-
quency
Description: Sets the denominator natural frequency for current setpoint filter 1 (PT2, general filter).
Dependency: The current setpoint filter 1 is activated via p1656.0 and parameterized via p1658 ... p1659.
p1659 *
Current setpoint filter 1
denominator damping
Description: Sets the denominator damping for current setpoint filter 1.
Dependency: The current setpoint filter 1 is activated via p1656.0 and parameterized via p1658 ... p1659.
p1663
Current setpoint filter 2
denominator natural fre-
quency
Description: Sets the denominator natural frequency for current setpoint filter 2 (PT2, general filter).
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1663 ... p1666.
p1664
Current setpoint filter 2
denominator damping
Description: Sets the denominator damping for current setpoint filter 2.
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1663 ... p1666.
p1665
Current setpoint filter 2
numerator natural fre-
quency
Description: Sets the numerator natural frequency for current setpoint filter 2 (general filter).
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
p1666
Current setpoint filter 2
numerator damping
Description: Sets the numerator damping for current setpoint filter 2.
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1663 ... p1666.
p1668
Current setpoint filter 3
denominator natural fre-
quency
Description: Sets the denominator natural frequency for current setpoint filter 3 (PT2, general filter).
Dependency: Current setpoint filter 3 is activated via p1656.2 and parameterized via p1668 ... p1671.
p1669
Current setpoint filter 3
denominator damping
Description: Sets the denominator damping for current setpoint filter 3.
Dependency: Current setpoint filter 3 is activated via p1656.2 and parameterized via p1668 ... p1671.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 07/2015, 6SL3298-0AV60-0BP0
Min
Max
0000 bin
1111 bin
0.5
16000.0
0.001
10.000
0.5
16000.0
0.001
10.000
0.5
16000.0
0.000
10.000
0.5
16000.0
0.001
10.000
Factory
Unit
Data
Setting
type
0001
-
U16
bin
1999.0
Hz
Float
0.700
-
Float
1000.0
Hz
Float
0.300
-
Float
1000.0
Hz
Float
0.010
-
Float
1000.0
Hz
Float
0.300
-
Float
Parameters
10.2 Parameter list
Effective
Can be
changed
IM
T, U
IM
T, U
IM
T, U
IM
T, U
IM
T, U
IM
T, U
IM
T, U
IM
T, U
IM
T, U