Control functions
7.7 Communicating with the PLC
● One byte for the byte count
● N bytes for the register vaules
Byte 1
Byte 2
Address
FC (0x06)
Operating steps
Description
Configure the RS485 bus address by parameter
p29004.
Select the communication protocol by parameter
p29007.
Select the command and setpoint source by parame-
ter p29008.
Set the transmission baud rate by parameter p29009.
Set control mode for the drive by p29003.
Save the parameters and restart the drive.
Configure the PLC parameters.
Write the control word via PLC.
Write the setpoint and read the status word via PLC.
186
Byte 3
Byte 4
Start ad-
Start ad-
dress
dress
(most
(least
significant
significant
byte)
byte)
Byte 5
Byte 6
Byte 7 +
n
Number of
Number of
nth value
registers
registers
(most
(most
(least
signifi-
significant
significant
cant
byte)
byte)
byte)
You can configure the slaver address from 1 to 31.
p29007 = 0: No protocol
p29007 = 1: USS protocol
p29007 = 2: Modbus protocol
p29008 = 1: Setpoint and control word from Modbus PZD
p29008 = 2: No control word.
5: 4800 baud
6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
13: 187500 baud
Note:
Keep the PLC baud rate the same as the drive setting.
Set even parity check for the PLC.
Note:
Bit 10 of the register 40100 must be set to 1 to allow the PLC
to control the drive.
You need to trigger a rise edge for OFF1 to enable SON sta-
tus for the motor, and OFF2 and OFF3 must be set to 1. The
step must be executed when you enable SON for the first
time.
Operating Instructions, 07/2015, 6SL3298-0AV60-0BP0
Byte 8 +
Byte 9 + n
Byte 10 +
n
n
nth value
CRC
CRC
(least
signifi-
cant
byte)
Comment
SINAMICS V90, SIMOTICS S-1FL6