Braking sequence
The operating principle of the holding brake is configured during motor selection for motors
with incremental encoders and configured automatically for motors with absolute encoders.
The start of the closing time for the brake depends on the expiration of the shorter of p1227
(zero speed detection monitoring time) and p1228 (pulse suppression delay time).
Parameter setting
You can configure the holding brake with the parameter p1215 according to the actual
application.
Parameter
Range
p1215
0 to 3
When you set p1215=1, the motor holding brake is open once the digital input signal SON
has a rising edge and becomes closed once a falling edge comes to SON.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 07/2015, 6SL3298-0AV60-0BP0
Factory setting
Unit
0
-
Configuration of the holding brake.
0: No holding brake available
1: Motor holding brake according to sequence control (SON)
2: Motor holding brake always open
3: SIEMENS internal use
Control functions
7.2 General functions
Description
141