Step
12
Configure necessary digital input signals by setting the
following parameters:
p29301[1]: DI1
p29302[1]: DI2
p29303[1]: DI3
p29304[1]: DI4
p29305[1]: DI5
p29306[1]: DI6
p29307[1]: DI7
p29308[1]: DI8
13
Check the encoder type and perform referencing:
For an incremental encoder, choose a referencing
mode by setting parameter p29240 and perform
referencing.
For an absolute encoder, adjust the encoder with
the BOP menu function "ABS". Refer to "Adjusting
an absolute encoder (Page 134)".
14
Set the pulse train encoder output.
15
Save parameters with the BOP.
16
Switch on the 3-phase 380 VAC power supply.
17
Clear faults and alarms.
18
Trigger the digital signal SON to be high level.
19
Select a fixed position setpoint by configuring the
digital inputs POS1, POS2 and POS3, then start posi-
tioning with the triggering signal P-TRG.
20
The system commissioning in internal position control
mode ends.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 07/2015, 6SL3298-0AV60-0BP0
Description
5.3 Commissioning in internal position control mode (IPos)
The factory settings are:
p29301[1]: 1 (SON)
p29302[1]: 2 (RESET)
p29303[1]: 3 (CWL)
p29304[1]: 4 (CCWL)
p29305[1]: 5 (G-CHANGE)
p29306[1]: 6 (P-TRG)
p29307[1]: 21 (POS1)
p29308[1]: 22 (POS2)
Refer to "Digital inputs/outputs (DIs/DOs) (Page 69)".
NOTE: If your encoder is an incremental encoder, you
must configure the digital input signal REF or SREF ac-
cording to your selection of referencing mode.
Refer to "Referencing (Page 162)".
Five referencing modes are available for the incremental
encoder:
p29240=0: with digital input signal REF
p29240=1 (default): external referencing cam (REF)
and encoder zero mark
p29240=2: only encoder zero mark
p29240=3: external referencing cam (CCWL) and
encoder zero mark
p29240=4: external referencing cam (CWL) and en-
coder zero mark.
Refer to "Referencing (Page 162)".
Refer to "PTO function (Page 155)".
Refer to "Diagnostics (Page 291)".
POS3 : POS2 : POS1
0 : 0 : 0: fixed position setpoint 1 (p2617[0])
0 : 0 : 1: fixed position setpoint 2 (p2617[1])
0 : 1 : 0: fixed position setpoint 3 (p2617[2])
0 : 1 : 1: fixed position setpoint 4 (p2617[3])
1 : 0 : 0: fixed position setpoint 5 (p2617[4])
1 : 0 : 1: fixed position setpoint 6 (p2617[5])
1 : 1 : 0: fixed position setpoint 7 (p2617[6])
1 : 1 : 1: fixed position setpoint 8 (p2617[7])
Refer to "Selecting a fixed position setpoint and starting
positioning (Page 171)".
You can check the system performance. If it is not satis-
fied, you can adjust it. Refer to "Tuning (Page 223)".
Commissioning
Remarks
113