Fault
F7475: EPOS: Target posi-
tion < start of traversing
range
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
F7476: EPOS: Target posi-
tion > end of the traversing
range
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
F7481: EPOS: Axis position <
software limit switch minus
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
F7482: EPOS: Axis position >
software limit switch plus
Reaction: OFF1 (OFF2,
OFF3)
Acknowledgement:
IMMEDIATELY
F7490: Enable signal with-
drawn while traversing
Reaction: OFF1
Acknowledgement:
IMMEDIATELY
F7491: STOP cam minus
reached
Reaction: OFF3
Acknowledgement:
IMMEDIATELY
F7492: STOP cam plus
reached
Reaction: OFF3
Acknowledgement:
IMMEDIATELY
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 07/2015, 6SL3298-0AV60-0BP0
Cause
The target position for relative traversing
lies outside the traversing range.
The target position for relative traversing
lies outside the traversing range.
The actual position of the axis is less than
the position of the software limit switch
minus.
The actual position of the axis is greater
than the position of the software limit
switch plus.
For a standard assignment, another
fault may have occurred as a result of
withdrawing the enable signals.
The drive is in the "switching on inhibit-
ed" state (for a standard assignment).
The STOP cam minus was reached. For a
positive traversing direction, the STOP
cam minus was reached, i.e. the wiring of
the STOP cam is incorrect.
The STOP cam plus was reached. For a
negative traversing direction, the STOP
cam plus was reached, i.e. the wiring of
the STOP cam is incorrect.
11.2 List of faults and alarms
Remedy
Correct the target position.
Correct the target position.
Correct the target position.
Change software limit switch minus (CI:
p2580).
Correct the target position.
Change software limit switch plus (CI:
p2581).
Set the enable signals or check the cause
of the fault that first occurred and then re-
sult (for a standard assignment).
Check the assignment to enable the basic
positioning function.
Leave the STOP cam minus in the posi-
tive traversing direction and return the ax-
is to the valid traversing range.
Check the wiring of the STOP cam.
Leave the STOP cam plus in the negative
traversing direction and return the axis to
the valid traversing range.
Check the wiring of the STOP cam.
Diagnostics
301