Installation and Connection

3.3.3 Mains connection

Mains connection 230 V 1-phase
3 x 1,5 mm²
1 x 230 V AC
Protection
• Fuse 10 A slow-blowing or power protective
Power protective switch
(D-/K-characteristic at size 04)
• RCD (fault current protective switch)
Type A (at size 04) / else type A or B
• at DC-supply pay attention to the permissible
voltage range of the fuses
DC-connection 230 V-class
2 x 1,5 mm²
250...370 V DC

3.3.4 Motor connection terminal strip X1.B

• PE
Connection for earthing
• U, V, W
Servo motor
• PA, PB
Braking resistor
• T1, T2
Temperature sensor / switch
10
X1.A
--
++
L3
N
N/L2
L1
L1
PE
PE
X1.A
-
--
+
++
L3
N/L2
L1
PE
Mains connection 230 V 3-phase
4 x 1,5 mm²
3 x 230 V AC
Mains connection 400 V 3-phase
4 x 1,5 mm²
3 x 400 V AC
DC-connection 400 V-class
2 x 1,5 mm²
420...720V DC
X1.A
--
++
L3
L3
L2
N/L2
L1
L1
PE
PE
X1.A
--
++
L3
L3
L2
L2
L1
L1
PE
PE
X1.A
-
--
+
++
L3
L2
L1
PE