1MRK 500 096-UUS B
Section 6
6.1

Normal operation

In a normal IED use situation, the basic operation includes monitoring and checking procedures.
Monitoring measured values
Checking object states
Checking function setting parameters
Checking events and alarms
All basic operations can be performed via the LHMI or with PCM600.
6.2

Disturbance identification

Disturbances and their causes can be identified by indicator LEDs: Normal, Pickup and Trip. During
normal operation, the Normal LED is steady green.
For the LEDs to operate, the disturbance recorder has to be defined in the configuration.
Table 21:
LED
Pickup LED
Trip LED
Further actions to be taken to identify the disturbance:
Checking alarm LEDs
Reading event history
Checking fault records
Analyzing disturbance recordings
650 series
Operation manual

IED operation

For more information, see PCM600 documentation.
Disturbance indications
Document the disturbance before clearing the information from the IED.
Only authorized and skilled personnel should analyze possible errors and decide on
further actions. Otherwise, stored disturbance data can be lost.
© Copyright 2013 ABB. All rights reserved
State
Yellow, steady
Red, steady
IED operation
GUID-25794CEB-1F3A-452E-92B4-DDAD6F058CAF v5
GUID-A1EB4334-DAF0-439E-8EB4-8ED02C610DAA v7
Description
Protection picked up
Protection tripped
Section 6
57