Signals In Double-Breaker Arrangement - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 11
Control
11.5.4.3
354

Signals in double-breaker arrangement

The busbar grounding switch is only allowed to operate if all disconnectors of the bus
section are open.
Section 1
(WA1)A1
(WA2)B1
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
DB_BUS
ANSI04000511 V1 EN
Figure 158:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
All disconnectors of this part of the busbar are open.
VP_BB_DC
The switch status of all disconnectors on this part of the busbar are valid.
EXDU_BB
No transmission error from any bay that contains the above information.
These signals from each double-breaker bay (DB_BUS) are needed:
Signal
189OPTR
189 is open.
289OPTR
289 is open.
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
EXDU_DB
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module
(A1A2_DC) is used for different busbars, that is, for both bus-section disconnectors
A1A2_DC and B1B2_DC.
Signal
DCOPTR
The bus-section disconnector is open.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
Section 2
A2
B2
BB_ES
DB_BUS
en04000511_ansi.vsd
1MRK 506 334-UUS A
Application manual