Data To Be Transferred Over The Serial Bus - ABB SPAU 140 C User Manual And Technical Description

Synchro-check relay
Table of Contents

Advertisement

Data to be
transferred over
the serial bus
In addition to the event code data transfer, the
input data (I data), output data (O data), set-
ting values (S), memorized data (V data) and
some other data can be read from the relay
Data
Input data
Measured voltage value U1
Measured voltage value U2
Measured voltage value U3
Measured voltage difference value U1-U3
Measured voltage difference value U2-U3
Measured frequency value of U3
Measured frequency difference value U1-U3
Measured frequency difference value U2-U3
Measured phase angle difference value U1-U3
Measured phase angle difference value U2-U3
External command signal CS13
External command signal CS23
External blocking signal BS13
External blocking signal BS23
Output data
Starting of SC13
(U
conditions are fulfilled)
max
SC13 closing
Starting of VC13
VC13 closing
Starting of SC23
(U
conditions are fulfilled)
max
SC23 closing
Starting of VC23
VC23 closing
Closing signal CB13
Closing signal CB23
Output signal ALARM
Operation of output relays, ENA signal
Memorized output signal ALARM
module over the serial communication bus.
Further, part of the data can be changed over
the SPA bus by separate commands. All data
information is available in channel 0.
Code
Data
Value
direction
I1
R
0.00 ... 1.3 x U
I2
R
0.00 ... 1.3 x U
I3
R
0.00 ... 1.3 x U
I4
R
0.00 ... 1.3 x U
I5
R
0.00 ... 1.3 x U
I6
R
45.0 ... 65.0 Hz
±0.00 ... ±20.0 Hz
I7
R
999 = not measurable
±0.00 ... ±20.0 Hz
I8
R
999 = not measurable
0 ... ±180°
I9
R
999 = not measurable
0 ... ±180°
I10
R
999 = not measurable
I11
R
0 = not active
1 = active
I12
R
0 = not active
1 = active
I13
R
0 = not active
1 = active
I14
R
0 = not active
1 = active
O1
R
0 = not started
1 = started
O2
R
0 = not closed
1 = closed
O3
R
0 = not started
1 = started
O4
R
0 = not closed
1 = closed
O5
R
0 = not started
1 = started
O6
R
0 = not closed
1 = closed
O7
R
0 = not started
1 = started
O8
R
0 = not closed
1 = closed
O9
R,W,(P) 0 = not active
1 = active
O10
R,W,(P) 0 = not active
1 = active
O11
R,W,(P) 0 = not active
1 = active
O41
R,W,(P) 0 = not operated
1 = operated
O21
R
0 = no alarm
1 = alarm
n
n
n
n
n
27