Examples Of Applications - ABB SPAU 130 C User Manual And Technical Description

Three-phase overvoltage and undervoltage relay
Table of Contents

Advertisement

Examples of
application
Example 1.
Network overvoltage
and undervoltage
supervision
10
A
N
dn
da
13 14 15
16 1718
19 20 21
U3
SPAU 130 C
Fig. 4. Substation overvoltage and undervoltage protection with voltage relay SPAU 130 C. The
selector switch positions are shown in the table on the following page.
The overvoltage and undervoltage relay module
SPCU 3C14 measures the phase-to-phase
voltages.
Many components of the power system are
sensitive to overvoltage. Inverse time character-
istic of the overvoltage relay is recommended as
the liability to damage of the power system
components often is a function of the duration
of the overvoltage. At inverse time characteristic
the relay provides an alarm signal at when the set
start voltage has been exceeded. If the voltage
exceeds 1.06 times the set start voltage the relay
operates, the faster the greater the voltage is.
L1
I
L2
L3
+
0
+
+
(~)
Uaux
-
(~)
BS
IRF
-
10 11
61 62
70 71 72
_
E
+ -
U3
SGR/1
IRF
t>,k>
3U>
SGB/5
t<
3U<
U1
Thus the overvoltage stage provides an alarm
signal when the overvoltage arises and trips the
circuit breaker, if the voltage continues to rise.
When the characteristic curve A is selected the
alarm level can be set low enough and still the
voltage regulator is granted time enough to
operate even during severe voltage fluctuations.
The undervoltage stage also trips the circuit
breaker. An unwanted operation of the under-
voltage stage during an autoreclose cycle can be
inhibited with switch SG1/6. If switch SG1/6 = 1
the operation of the undervoltage stage is inhib-
ited, when the voltage falls below 20% x U
I
+
0
-
0
+
-
I
+
START1
SIGNAL1
TRIP2
+
77 78
80 81
68 69
D
C
B
1
1
1
SGR
3 2 4
7
5
8
SS1
TS1
SS2
TS2
I/O
-
0
-
I
Rx
Tx
TRIP1
+
SERIAL
PORT
65 66
A
1
6
U2
.
n

Advertisement

Table of Contents
loading

Table of Contents