Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
TRAVEL_CAL
Travel Count
TVL_COUNT
Travel Hi Calibration
TVL_HI_CAL
Travel Lo Calibration
TVL_LO_CAL
Travel Crossover
TVL_CROSSOVER
Travel Fac Hi
TVL_FAC_HI
Travel Fac Lo
TVL_FAC_LO
Travel IP Bias
TVL_IP_BIAS
Travel MLFB Bias
TVL_MLFB_BIAS
Last Calibration Type
TVL_CAL_TYPE
TRAVEL_TUNE
Travel Integral Enable
TVL_INTEG_ENABLE
Travel Integral Limit Hi
TVL_INTEG_LIM_HI
Travel Integral Limit Lo
TVL_INTEG_LIM_LO
Travel Integral Dead Zone
TVL_INTEG_DEADZ
Travel MLFB Gain
TVL_MLFB_GAIN
Index
RO /
Mode
Number
RW
43
43.1
RO
N/A
<TVL_FAC_HI
MAN
43.2
RW
>TVL_LO_CAL
OOS
>TVL_FAC_LO
MAN
43.3
RW
<TVL_HI_CAL
OOS
MAN
43.4
RW
>0% < = 100%
OOS
43.5
RO
N/A
43.6
RO
N/A
MAN
43.7
RW
0% - 100%
OOS
MAN
43.8
RW
0 - 100%
OOS
0: Not Calibrated
MAN
1: Single Point Calibration
43.9
RW
OOS
2: Auto Calibration
3: Manual Calibration
44
MAN
1=Off
44.1
RW
OOS
2=On
MAN
44.2
RW
0% - 100%
OOS
MAN
44.3
RW
-100% - 0%
OOS
MAN
44.4
RW
0% - 2%
OOS
MAN
> = 0
44.5
RW
OOS
Range
Initial Value
50%
Set by Factory
Set by Factory
70%
50%
2: Auto Calibration CAL
2=On
30%
-30%
0.25%
35
-Continued-
Detailed Setup—Transducer Block
Protect
Description
Category
Data Type: Uint16
Raw feedback from Travel Sensor
Data Type: Uint16
CAL
Maximum drive calibration point
Data Type: Uint16
CAL
Minimum drive calibration point
Data Type: Float
CAL
Not used for the DVC6200f
Data Type: Uint16
N/A
Maximum value of travel sensor
counts. Set at factory.
Data Type: Uint16
N/A
Minimum value of travel sensor
counts. Set at factory.
CAL
Data Type: Float
CAL
Data Type: Float
Data Type: Enum (Uint8)
SETUP
Data Type: Enum (Uint8)
SETUP
Data Type: Float
SETUP
Data Type: Float
SETUP
Data Type: Float
SETUP
Data Type: Float
July 2013