Fisher FIELDVUE DVC6200f Instruction Manual page 135

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐31. BLOCK_ERR Conditions
Condition Number
0
Other (N/A)
1
Block Configuration Error—SHED_OPT or BYPASS set to 0
2
Link Configuration Error (N/A)
3
Simulate Active (N/A)
4
Local Override—The actual mode is LO and Track Enable is set.
5
Device Fault State Set (N/A)
6
Device Needs Maintenance Soon (N/A)
7
Input failure/process variable has Bad status—The parameter linked to IN is indicating a Bad status.
8
Output Failure (N/A)
9
Memory Failure (N/A)
10
Lost Static Data (N/A)
11
Lost NV Data (N/A)
12
Readback Check Failed (N/A)
13
Device Needs Maintenance Now (N/A)
Power Up—Set if devices was powered up with this block in Out of Service (OOS) mode. Cleared on first change of mode to other
14
than OOS.
15
Out of Service—The actual mode is Out of Service (OOS).
PID Function Block Parameter List (table 4‐32)
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shaded Index Number indicates sub‐parameter
Table 4‐32. PID Function Block System Parameters Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Index
RO /
Block
Number
RW
Mode
1
RO
N/A
0 to 65535
2
RW
ALL
7 bit ASCII
3
RW
ALL
0 to 65535
4
RW
ALL
0 to 255
5
OOS, MAN, AUTO
5.1
RW
ALL
CAS, RCAS, ROUT
5.2
RO
ALL
OOS+MAN+AUTO+
5.3
RW
ALL
CAS+RCAS+ROUT
5.4
RW
ALL
Condition Name and Description
Range
Initial Value
0
Spaces
0
0
OOS until
block is
configured,
then last valid
target
OOS
OOS MAN,
AUTO CAS,
RCAS ROUT
AUTO
-Continued-
Detailed Setup—PID Function Block
Description
Data Type: Unsigned16
The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static pa rameter value in
the block is changed.
Data Type: Octet String
The user description of the intended application of
the block.
Data Type: Unsigned16
The strategy field can be used to identify grouping
of blocks. This data is not checked or processed by
the block.
Data Type: Unsigned8
The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.
Data Type: DS‐69
Valid Bits: 7: OOS, 6: IMAN, 5: LO, 4: MAN, 3:
AUTO, 2: CAS, 1: RCAS, 0: ROUT
The actual, target, permitted, and normal modes
of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
July 2013
133