Fisher FIELDVUE DVC6200f Instruction Manual page 105

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
INST_ALERTS_ENABLE
Electronics Enable
ELECT_ENABLE
Sensor Enable
SENSOR_ENABLE
Environment Enable
ENVIRO_ENABLE
Travel Enable
TRAVEL_ENABLE
Proximity Enable
PROX_ENABLE
Travel History Enable
TVL_HISTORY_ENABLE
Performance Enable
PERF_ENABLE
Index
RO /
Mode
Number
RW
75
0: Drive Current
1: Drive Signal
2: Program Memory
3: Static Memory
75.1
RW
ALL
4: Processor
5: I/O Processor
6: Output Block Timeout
7: Blocks Set to Defaults
0: Travel Sensor
1: Port A Pressure Sensor
2: Port B Pressure Sensor
75.2
RW
ALL
3: Supply Pressure
Sensor
4: Temperature Sensor
0: Supply Pressure High
1: Supply Pressure Low
75.3
RW
ALL
2: Temperature High
3: Temperature Low
0: Travel Deviation
1: Travel High High
75.4
RW
ALL
2: Travel Low Low
3: Travel High
4: Travel Low
0: Travel Open
1: Travel Closed
2: Proximity High High
75.5
RW
ALL
3: Proximity High
4: Proximity Low
5: Proximity Low Low
0: Cycle Counter
75.6
RW
ALL
1: Travel Accumulator
0: Performance Critical
1: Performance Reduced
75.7
RW
ALL
2: Performance
Information
Range
Initial Value
Enabled Bits:
0: Drive Current
1: Drive Signal
2: Program
Memory
3: Static Memory
4: Processor
5: I/O Processor
7: Block Set to
Default
Enabled Bits:
0: Travel Sensor
1: Port A Pressure
Sensor
2: Port B Pressure
Sensor
3: Supply Pressure
Sensor
4: Temperature
Sensor
Enabled Bits:
0: Supply Pressure
High
2: Temperature
High
3: Temperature
Low
Enabled Bits:
0: Travel
Deviation
All bits: 0
All bits: 0
Enabled Bits:
0: Performance
Critical
1: Performance
Reduced
-Continued-
Detailed Setup—Transducer Block
Protect
Description
Category
Data Type: Bit String (4 byte)
0=disable
SETUP
1=enable
Electronic Alerts Enable
Data Type: Bit String (4 byte)
0=disable
SETUP
1=enable
Sensor Alerts Enable
Data Type: Bit String (4 byte)
0=disable
SETUP
1=enable
Environment Alerts Enable
Data Type: Bit String (4 byte)
0=disable
SETUP
1=enable
Travel Alerts Enable
Data Type: Bit String (4 byte)
0=disable
SETUP
1=enable
Proximity Alerts Enable
Data Type: Bit String (4 byte)
0=disable
SETUP
1=enable
Travel History Alerts Enable
Data Type: Bit String (4 byte)
0=disable
SETUP
1=enable
Performance Alerts Enable
July 2013
103

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents