Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Basic Setup
BASIC_SETUP
Actuator Style
ACTUATOR_STYLE
Zero Power Condition
ZERO_PWR_COND
Travel Sensor Motion
TRAVEL_SEN_MOTION
Feedback Connection
FEEDBACK_CONN
Relay Type
RELAY_TYPE
Maximum Supply Pressure
MAX_SUPP_PRESS
Pressure Range Hi
PRESS_RANGE_HI
Pressure Range Lo
PRESS_RANGE_LO
Travel Calibration Trigger
TVL_CAL_TRIGGER
Travel Tuning Set
TVL_TUNING_SET
Pressure Tuning Set
PRESS_TUNING_SET
92
Index
RO /
Mode
Number
RW
42
1=Spring & Diaphragm
2=Piston‐Dbl w/o Spring
MAN
42.1
RW
3=Piston‐Dbl w/Spring
OOS
4=Piston Sgl w/Spring
MAN
1=Valve Closed
42.2
RW
OOS
2=Valve Open
MAN
1=Counter Clockwise
42.3
RW
OOS
2=Clockwise
100: Default Array
64: SStem #19 Array
65: SStem #25 Array
66: SStem #38 Array
67: SStem #50 Array
70: SStem #100 Array
74: SStem #200 Array
MAN
42.4
RW
OOS
85: SStem #1 Roller
Array
90: RShaft End Array
95: RShaft #1 Window
Array
97: RShaft #2 Window
Array
1=Relay A or C‐‐Double or
Single Direct
2=Relay B‐‐Single Reverse
5=Relay C‐Special App.
‐‐Single Direct
6=Relay B‐Special App.
‐‐Single Reverse
9=Lo‐Bleed Relay A or
MAN
C‐‐Double or Single
42.5
RW
OOS
Direct
10=Lo‐Bleed Relay B‐‐
Single Reverse
13=Lo‐Bleed Relay
C‐Special App.‐‐Single
Direct
10=Lo‐Bleed Relay
B‐Special App.‐-Single
Reverse
MAN
> 0, < = 150
42.6
RW
OOS
MAN
> 0, < = 150
42.7
RW
OOS
MAN
> = 0, < = 150
42.8
RW
OOS
MAN
42.9
RW
1 = Aux Term ignored
OOS
MAN
1=B, 2= C, ...12=M
42.10
RW
OOS
23=X
MAN
1=B, 2=C, ...12= M
42.11
RW
OOS
23=X
Range
Initial Value
1=Spring &
Diaphragm
1=Valve Closed
1=Counter
Clockwise
=Relay A or
C‐‐Double or
Single Direct
35 psig
15.0 psig
3.0 psig
1
2=C
2=C
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
SETUP
Data Type: Enum (Uint8)
Data Type: (Uint8)
Enum Identifies whether the valve is
SETUP
open or closed when instrument
power is lost.
SETUP
Data Type: Enum (Uint8)
SETUP
Data Type: Enum (Uint8)
SETUP
Data Type: Enum (Uint8)
SETUP
Data Type: Float
Data Type: Float
Defines pressure corresponding to
SETUP
max pressure in pressure control
mode.
Data Type: Float
Defines pressure corresponding to
SETUP
minimum pressure in pressure
control mode.
SETUP
Not available in the DVC6200f
Data Type: Enum (Uint8)
SETUP
Letter (B through M or X)
Data Type: Enum (Uint8)
SETUP
Letter (B through M or X)