Fisher FIELDVUE DVC6200f Instruction Manual page 94

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Basic Setup
BASIC_SETUP
Actuator Style
ACTUATOR_STYLE
Zero Power Condition
ZERO_PWR_COND
Travel Sensor Motion
TRAVEL_SEN_MOTION
Feedback Connection
FEEDBACK_CONN
Relay Type
RELAY_TYPE
Maximum Supply Pressure
MAX_SUPP_PRESS
Pressure Range Hi
PRESS_RANGE_HI
Pressure Range Lo
PRESS_RANGE_LO
Travel Calibration Trigger
TVL_CAL_TRIGGER
Travel Tuning Set
TVL_TUNING_SET
Pressure Tuning Set
PRESS_TUNING_SET
92
Index
RO /
Mode
Number
RW
42
1=Spring & Diaphragm
2=Piston‐Dbl w/o Spring
MAN
42.1
RW
3=Piston‐Dbl w/Spring
OOS
4=Piston Sgl w/Spring
MAN
1=Valve Closed
42.2
RW
OOS
2=Valve Open
MAN
1=Counter Clockwise
42.3
RW
OOS
2=Clockwise
100: Default Array
64: SStem #19 Array
65: SStem #25 Array
66: SStem #38 Array
67: SStem #50 Array
70: SStem #100 Array
74: SStem #200 Array
MAN
42.4
RW
OOS
85: SStem #1 Roller
Array
90: RShaft End Array
95: RShaft #1 Window
Array
97: RShaft #2 Window
Array
1=Relay A or C‐‐Double or
Single Direct
2=Relay B‐‐Single Reverse
5=Relay C‐Special App.
‐‐Single Direct
6=Relay B‐Special App.
‐‐Single Reverse
9=Lo‐Bleed Relay A or
MAN
C‐‐Double or Single
42.5
RW
OOS
Direct
10=Lo‐Bleed Relay B‐‐
Single Reverse
13=Lo‐Bleed Relay
C‐Special App.‐‐Single
Direct
10=Lo‐Bleed Relay
B‐Special App.‐-Single
Reverse
MAN
> 0, < = 150
42.6
RW
OOS
MAN
> 0, < = 150
42.7
RW
OOS
MAN
> = 0, < = 150
42.8
RW
OOS
MAN
42.9
RW
1 = Aux Term ignored
OOS
MAN
1=B, 2= C, ...12=M
42.10
RW
OOS
23=X
MAN
1=B, 2=C, ...12= M
42.11
RW
OOS
23=X
Range
Initial Value
1=Spring &
Diaphragm
1=Valve Closed
1=Counter
Clockwise
=Relay A or
C‐‐Double or
Single Direct
35 psig
15.0 psig
3.0 psig
1
2=C
2=C
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
SETUP
Data Type: Enum (Uint8)
Data Type: (Uint8)
Enum Identifies whether the valve is
SETUP
open or closed when instrument
power is lost.
SETUP
Data Type: Enum (Uint8)
SETUP
Data Type: Enum (Uint8)
SETUP
Data Type: Enum (Uint8)
SETUP
Data Type: Float
Data Type: Float
Defines pressure corresponding to
SETUP
max pressure in pressure control
mode.
Data Type: Float
Defines pressure corresponding to
SETUP
minimum pressure in pressure
control mode.
SETUP
Not available in the DVC6200f
Data Type: Enum (Uint8)
SETUP
Letter (B through M or X)
Data Type: Enum (Uint8)
SETUP
Letter (B through M or X)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents