Fisher FIELDVUE DVC6200f Instruction Manual page 82

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—Transducer Block
July 2013
PD Run
PD Run enables or disables Performance Diagnostics in the instrument (PD Inside). Selecting PD Off disables PD Inside.
Selecting PD On enables PD Inside.
Performance Critical
D Performance Critical Alert—This alert is active if the instrument is no longer able to control the valve or performance
has been dramatically reduced.
D Performance Critical Alert Enable—When enabled Performance Critical Alert Enable activates the Performance
Critical Alert.
Performance Reduced
D Performance Reduced Alert—This alert is active if the instrument has detected a reduction in performance.
D Performance Reduced Alert Enable—When enabled Performance Reduced Alert Enable activates the Performance
Reduced Alert.
Performance Information
D Performance Information Alert—This alert is active if the instrument has detected a condition that may pertain to
control performance.
D Performance Information Alert Enable—When enabled Performance Information Alert Enable activates the
Performance Information Alert.
PlantWeb Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable
Field Communicator
D Failed Enable—Failed Enable (FAILED_ENABLE [62]) enables or disables conditions that can cause a failed alert. A
failed alert indicates a failure within the device that will make the device or some part of the device non‐operational.
Table C‐2 lists the available PlantWeb alerts.
D Maintenance Enable—Maintenance Enable (MAINT_ENABLE [63]) enables or disables conditions that can cause a
maintenance alert. A maintenance alert indicates the device or some part of the device needs maintenance soon.
Table C‐2 lists the available PlantWeb alerts.
D Advise Enable—Advise Enable (ADVISE_ENABLE [64]) enables or disables conditions that can cause an advisory alert.
An advisory alert indicates informative conditions that do not have a direct impact on the device's primary
functions. Table C‐2 lists the available PlantWeb alerts.
PlantWeb Alert Reporting
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting
Field Communicator
D Failed Suppress—Failed Suppress (FAILED_MASK [65]) determines which of the failed alert conditions are
suppressed so that they are not reported. Even if reporting is suppressed, the bit in Failed Active (FAILED_ACTIVE
[59]) is still set.
D Maintenance Suppress—Maintenance Suppress (MAINT_MASK [66]) determines which of the maintenance alert
conditions are suppressed so that they are not reported. Even if reporting is suppressed, the bit in Maintenance
Active (MAINT_ACTIVE [60]) is still set.
80
Instruction Manual
D103412X012