Detailed Setup—Resource Block
July 2013
Table 4‐3. Resource Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Features Selected
FEATURE_SEL
Cycle Type
CYCLE_TYPE
Cycle Selection
CYCLE_SEL
Minimum Cycle Time
MIN_CYCLE_T
Memory Size
MEMORY_SIZE
Nonvolatile Cycle Time
NV_CYCLE_T
Free Space
FREE_SPACE
Free Time
FREE_TIME
RCAS Timeout
SHED_RCAS
56
Index
RO /
Mode
Number
RW
1: Reports Supported
2: Fault State
supported
18
RW
ALL
3: Software Write lock
supported
10:Reannunciation
supported
19
RO
NA
0: Scheduled
20
ALL
0: Scheduled
21
RO
NA
3200
22
RO
NA
45
23
RO
NA
Positive
24
RO
NA
0 to 100%
25
RO
NA
0 to 100%
26
RW
ALL
Positive
-Continued-
Initial
Range
Value
Data Type: Bit String
1:0
0 = Inactive
2:1
1 = Active
3:1
Shows the selected resource block options. For
10:0
details see Device Features in this section.
Data Type: Bit String
0 = Inactive
1 = Active
0: 1
Identifies the block execution methods available
for this resource, may be scheduled, completion
of block execution
Data Type: Bit String
0 = Inactive
1 = Active
0: 0
Identifies the block execution method selected
for this resource.
Data Type: Unsigned32
Time duration of the shortest cycle interval (in
1/32 millisecond) of which the resource is
3200
capable. In the digital valve controller this value
is fixed at 3200 (100 milliseconds).
Date Type: Unsigned16
Memory, in kilobytes, available for additional
function blocks. Because no additional function
45
blocks may be added to DVC6200f instruments,
this parameter value is fixed at 45.
Date Type: Unsigned32
This parameter identifies the minimum time
interval (in 1/32 milliseconds) between copies of
NV class data to NV memory. NV memory is
updated only if there has been a change in the
dynamic value. The last value saved in NV
memory will be available for the restart
procedure or a power cycle. A non‐zero value
576,000
regulates the frequency of writes, thus
protecting the life span of the device. If the value
is zero, data will never be automatically copied.
Changes made by other than publishing to NV
parameters will be copied to non‐volatile
memory immediately. For DVC6200f
instruments, this parameter value is fixed at
576,000 (18 seconds).
Data Type: Float
Percent of memory available for additional
function blocks (see also MEMORY_SIZE).
0
Because no additional function blocks may be
added to DVC6200f instruments, this parameter
value is fixed at 0.
Data Type: Float
Percent of block processing time that is free to
process additional blocks. Because no additional
0
function blocks may be added to DVC6200f
instruments, this parameter value is fixed at 0.
Date Type: Unsigned32
Time duration (in 1/32 millisecond) at which to
give up on computer writes to function block
RCAS parameters. If this time is exceeded then
640000
the function block will change to a mode other
than RCAS based on the SHED_OPT parameter
setting. Shed from RCAS mode never happens
when SHED_RCAS is set to zero.
Instruction Manual
D103412X012
Description