Fisher FIELDVUE DVC6200f Instruction Manual page 125

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐25. Analog Output Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Fault State Value
FSTATE_VAL
Back Calculation Output
BKCAL_OUT
Remote Cascade Input
RCAS_IN
Shed Options
SHED_OPT
Remote Cascade Output
RCAS_OUT
Update Event
UPDATE_EVT
UNACKNOWLEDGED
UPDATE_STATUS
TIME_STAMP
STATIC_REVISION
RELATIVE_INDEX
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Index
RO /
Block
Number
RW
Mode
24
ALL
PV Scale +/- 10%
Status Limits
25
RO
N/A
Value
Status
26
ALL
Value
Defined by FF spec
0=Invalid
1=Normal Shed,
Normal Return
2=Normal Shed, No
Return
3=Shed to Auto,
normal return
4=Shed to Auto, no
return. Target mode
changes to Auto on
detection of a shed
condition
27
ALL
5=Shed to Manual,
normal return
6=Shed to Manual, No
return. Target mode
changes to MAN on
detection of a shed
condition.
7=Shed to retained
target, normal return
8=Shed to retained
target, no return.
(Change target to
retained target)
Status
28
RO
N/A
Value
29
0:Undefined
29.1
RW
N/A
1:Acknowledged
2:
0:Undefined
29.2
RO
N/A
1:Update reported
2:Update not reported
29.3
RO
N/A
29.4
RO
N/A
29.5
RO
N/A
30
0:Undefined
30.1
RW
N/A
1:Acknowledged
2:
0:Undefined
1:Clear reported
30.2
RO
N/A
2:Clear not reported
3:Active reported
4:Active not reported
30.3
RO
N/A
30.4
RO
N/A
30.5
RO
N/A
Initial
Range
Value
0
Dynamic
BAD: NoCom:
NoVal:
const
0 Trk
0
Dynamic
0: Undefined
Unacknowledged
0: Undefined
0
0
0
0: Undefined
Unacknowledged
0: Undefined
0
0
0
-Continued-
Detailed Setup—AO Function Block
Description
Data Type: Float
Preset value to use if I/O_OPTS Fault State to Value
or Use Fault State Value on Restart is set.
Data Type: DS‐65
status required by the BKCAL_IN input of another
block to prevent reset windup and to provide
bumpless transfer to closed loop control.
Data Type: DS‐65
Target SP and status by supervisory host
Data Type: Unsigned8
Defines the action to be taken when the set point is
not updated in a remote mode.
Data Type: DS‐65
Block set point and status after ramping
Data Type: DS‐73
This alert is generated by any changes to static data.
Data Type: DS‐72
The block alarm is used for all configuration,
hardware, connection failure, or system problems
in the block.
July 2013
The value and
123

Hide quick links:

Advertisement

Table of Contents
loading