Fisher FIELDVUE DVC6200f Instruction Manual page 89

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Transducer Block Parameter List
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Protection Category: Indicates whether or not the parameter is writable while the PROTECTION parameter
 is set to a particular level.
-N/A indicates a read‐only parameter that is never writable, regardless of the value of the PROTECTION parameter
-NONE indicates a read‐only parameter that is always writable, regardless of the value of the PROTECTION parameter
-CAL indicates a parameter that is only writable while the value of the PROTECTION parameter is "NONE".
-SETUP indicates a parameter that is only writable while the value of the PROTECTION parameter is "NONE" or "CAL".
-ALL indicates a parameter that is writable while the value of the PROTECTION parameter is "NONE", "CAL", or "SETUP & CAL".
D Double indentation and shaded Index Number indicates sub‐parameter
Table 4‐14. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Index
RO /
Mode
Number
RW
1
RO
N/A
0 to 65535
2
RW
ALL
3
RW
ALL
0 to 65535
4
RW
ALL
1 to 255
5
5.1
RW
ALL
5.2
RO
N/A
3: AUTO
4: MANUAL
5.3
RW
ALL
7: OOS
5.4
RW
ALL
3: Simulate Active
10: Static Memory Failed
(Functional or thermal
data missing)
6
RO
N/A
13: Maintenance
Needed Now
(Functional or thermal
data missing)
15: Out‐of‐Service
Range
Initial Value
N/A
NULL
0
1
7: OOS
N/A
3:AUTO
4:MANUAL
7: OOS
3:AUTO
N/A
-Continued-
Detailed Setup—Transducer Block
Protect
Description
Category
Data Type: Uint16
The revision level of the static data.
Increments by one each time a static
N/A
parameter is written. The value is
reset to 0 whenever a Restart with
Defaults is performed. See
Restarting the Instrument.
Data Type: String
SETUP
The description of the block.
Data Type: Uint16
SETUP
Used to help group blocks.
Data Type: Uint8
The identification number of the
plant unit. Devices in a loop or plant
SETUP
section can be assigned with a
common alert key to aid the
operator in determining location of
alerts.
Data Type: DS‐69
The actual, target, permitted, and
normal modes.
NONE
Target: The requested block mode
N/A
Actual: The current mode of
the block
Permitted: Allowed modes for
NONE
Target
Normal: Most common mode
NONE
for Target
Data Type: Bit String (2 byte)
Error status associated with
N/A
hardware or firmware for the
transducer block.
July 2013