Fisher FIELDVUE DVC6200f Instruction Manual page 96

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
TRAVEL_CAL_RUN
Travel Calibration Command
TVL_CAL_CMD
Travel Calibration Prog
TVL_CAL_PROG
Travel Calibration Status
TVL_CAL_STATUS
Reserved
TVL_CAL_RESERVED
94
Index
RO /
Mode
Number
RW
45
1: Operating
2: Autocalibrate
3: Not Used by DVC6200f
4: Mark Full Open
5: Mark Full Closed
6: Manual Calibrate Final
7: Abort
8: Clear Cal Status
9: Manual Calibrate Init
10: Manual Calibrate
Restore
11: Reset Travel Sensor
Error
45.1
RW
MAN
12: Reserved
13: Execute Performance
Tuner
14: Execute Performance
Tuner (Graphite Packing)
16: Execute Performance
Tuner (Booster)
17: Execute Performance
Tuner (Graphite Packing
and Booster)
19: Autocalibration, Set
Filter
20: Autocalibrate
Extended, Set Filter
45.2
RO
N/A
0: auto cal complete
1: calibration complete
2: auto cal in progress
3: manual cal in progress
3: Not Used by DVC6200f
5: upper position marked
6: lower position marked
7: calibration error
8: Performance Tuner
45.3
RO
N/A
active
9: Performance Tuner
Success
10: Performance Tuner
Error (No movement)
11: Performance Tuner
Error (Accessories
unstable)
12: Performance Tuner
Error (Other)
45.4
Range
Initial Value
1=Operating
0%
no bits set
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
Data Type: Enum (Uint8)
CAL
Resets to 1 after a write
N/A
Data Type: Uint8
Data Type: Bit String (2 bytes)
All bits set to 0 when mode changes
N/A
from OOS. 0 = FALSE,
1 = TRUE
Reserved

Hide quick links:

Advertisement

Table of Contents
loading