Fisher FIELDVUE DVC6200f Instruction Manual page 199

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐72. Discrete Output Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
I/O Options
IO_OPTS
Status Options
STATUS_OPTS
Readback Discrete
READBACK_D
Cascade Input Discrete
CAS_IN_D
DO Channel
CHANNEL
Fault State Time
FSTATE_TIME
Fault State Value Discrete
FSTATE_VAL_D
Back Calculation Output Discrete
BKCAL_OUT_D
Remote Cascade Input Discrete
RCAS_IN_D
Index
RO /
Mode
Number
RW
Valid Bits
0: Invert
1: SP tracks PV in Man
3: SP tracks PV in LO
4: SP Track retained
target in Man or LO
6: Fault State to value
 0: freeze
 1: go to Fault State
14
OOS
value
7: Use Fault State value
on restart
8: Target to Man if Fault
State activated
9: Use PV for
BKCAL_OUT
4: Propagate Failure
15
OOS
Backward
16
RO
N/A
Status
17
ALL
Value
0=undefined
18
OOS
22=Setpoint (D)
19
ALL
Positive
20
ALL
21
RO
N/A
Status
22
ALL
Value
Range
Initial Value
All bits: 0
0: SP
1: PV
All bits: 0
Dynamic
BAD:
NC:
const
0
22=
Setpoint (D)
0
0
Dynamic
BAD:
NoCom:
NoVal:
const
0
-Continued-
Detailed Setup—DO Function Block
Description
Data Type: Bit String
0=Disable
1=Enable
Allows you to select the type of tracking and the
output value when a fault condition occurs.
Supported I/O options for the DO function block are
SP Tracks PV in Man, SP Tracks PV in LO, SP Tracks
Retained Target in Man or LO, Fault State to Value,
Use Fault state on Restart, Target to Man if Fault
State Activated, and Use PV for BKCAL_OUT.
Data Type: Bit String
0=Disable
1=Enable
Options the user may select for the block processing
of status.
Data Type: DS‐66
0=closed, 1=open, 5, 10, 15, 30...etc. are position in
5% increments.
Data Type: DS‐66
The remote set point value from another block.
Data Type: Unsigned16
Defines which transducer parameter receives the
DO output. Select Setpoint (D) to control valve
position.
Data Type: Float
Time from detection of a fault in the remote set
point to the Fault State output action.
Date Type: Unsigned8
Preset discrete SP_D value to use if I/O_OPTS Fault
State to Value is set.
Data Type: DS‐66
The value and status required by the BKCAL_IN_D
input of another block for output tracking
Date Type: DS‐66
Target set point and status provided by a
supervisory host to a discrete control or output
block.
July 2013
197