Travel Sensor Span Error—Indicates that span between the endpoints of travel are not far enough apart. This error is
reported during automatic calibration.
MLFB Error—Indicates that the Minor Loop Feedback sensor gave a non‐valid value during automatic calibration.
Travel Sensor Hi Error—Indicates the travel sensor has reported a travel position that is significantly above the normal
operating range, and has failed.
Travel Sensor Lo Error—Indicates the travel sensor has reported a travel position that is significantly below the normal
operating range, and has failed.
Pressure B Sensor Failure—Indicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
Pressure A Sensor Failure—Indicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
Supply Sensor Failure—Indicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
IOP Failure—Indicates the I/O processor has failed.
Drive Current Alert—Indicates that the Drive Current has exceeded the Drive Current Alert Point for more than the Drive
Current Alert Time.
Simulate Jumper ON—Indicates the simulate jumper is connected to the DVC6200f between the two AUX terminals.
Block Error
Table 6‐2 lists conditions reported in the BLOCK_ERR [6] and XD_ERROR [11] parameters. Conditions in italics are not
applicable for the transducer block and are provided only for your reference.
Table 6‐2. Transducer Block BLOCK_ERR and XD_ERROR Conditions
Condition Number
0
Other ‐ (N/A)
Block Configuration Error ‐ Indicates that one of the following parameters have been configured out of the proper range: 15,
1
16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
2
Link Configuration Error ‐ (N/A)
Simulate Active ‐ Indicates that alerts are being simulated. This is not an indication that the I/O blocks are using simulation
3
data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].
4
Local Override ‐ (N/A)
5
Device Fault State - (NA)
6
Maintenance Needed Soon ‐ (N/A)
7
Input failure/process variable has Bad status ‐ (N/A)
8
Output failure ‐ (N/A)
9
Memory failure ‐ (N/A)
10
Lost Static Data ‐ Indicates that manufacturing functional or thermal tests were incomplete
11
Lost NV Data ‐ (N/A)
12
Readback Check Failed ‐ (N/A)
13
Device Needs Maintenance Now ‐ Indicates that manufacturing functional or thermal tests were incomplete
14
Power Up ‐ (N/A)
15
Out of Service ‐ Indicates Out of Service Mode.