Fisher FIELDVUE DVC6200f Instruction Manual page 175

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐54. Channel Selections for the Analog Input Function Block
Channel
Parameter
2
TRAVEL_TARGET
3
FINAL_POSITION_VALUE
4
TRAVEL
5
SUPPLY_PRESS
6
PRESSURE_A
7
PRESSURE_B
8
PRESSURE_DIFF
9
DRIVE_SIGNAL
10
TRAVEL_DEVIATION
11
TEMPERATURE
12
CYCLE_COUNT
13
TRAVEL_ACCUMULATION
1. Refer to table 4‐14 for transducer block parameter descriptions and table 4‐25 for AO parameter descriptions.
Status Handling
The AI block only gets Good Non‐Specified Unlimited or Bad Device Failure for status from the transducer. This is
reflected in FIELD_VAL.STATUS [19.1]. PV.STATUS [7.1] is the same as FIELD_VAL.STATUS [19.1]. OUT.STATUS [8.1]
can also reflect Bad, Out of Service in addition to PV.STATUS [7.1] values.
In the STATUS_OPTS [14] parameter, you can select from the following options to control the status handling:
Propagate Fail Forward—If the status from the sensor is Bad, Device failure or Bad, Sensor failure, propogate it to OUT
without generating an alarm. The use of these sub‐status in OUT is determined by this option. Through this option,
you may determine whether alarming (sending out an alert) will be done by the block or propagated downstream for
alarming.
Figure 4‐25. Analog Input Function Block Timing Diagram
FIELD_VAL
PV_FTIME
Uncertain if in Manual mode—The status of the Output is set to Uncertain when the mode is set to Manual.
Note
1. The instrument must be in Out of Service mode to set the status option.
2. The AI block only supports the Uncertain if in Manual and Propagate failure. Unsupported options are not grayed out; they
appear on the screen in the same manner as supported options.
(1)
Block
Index Number
TB
TB
TB
TB
TB
TB
TB
TB
TB
TB
TB
TB
OUT (mode in man)
OUT (mode in auto)
PV
63% of Change
TIME (seconds)
49
17
34
35
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
36
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
37
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
38
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
53
52
48
73
72
Detailed Setup—AI Function Block
XD_SCALE Units
% (1342)
% (1342)
% (1342)
% (1342)
% (1342)
_C (1001), _F (1002)
no units (1588)
% (1342)
July 2013
173

Hide quick links:

Advertisement

Table of Contents
loading