PlantWeb Alerts
July 2013
Table C‐3. Using PlantWeb Alerts (Continued)
PlantWeb Alert
Alert Condition
(Group)
(Default Alert Category
Pressure Fallback
Pressure Fallback
(Sensors)
(Enabled)
(Maintenance)
Supply Pressure
Supply Press High
(Environment)
(Enabled)
(Maintenance)
Supply Press Low
(Enabled)
Temperature Limit
Temperature High
(Environment)
(Enabled)
(Advisory)
Temperature Low
(Enabled)
284
What the Alert is Detecting
(Default)
A travel sensor failure or large
travel deviation has resulted in
fallback to pressure control.
The supply pressure has
exceeded the Supply Pressure
Hi Alert Point.
The supply pressure is lower
than the Supply Pressure Lo
Alert Point.
The temperature is greater
than the Temperature Hi Alert
Point.
The temperature is lower than
the Temperature Lo Alert
Point.
Effect on Valve/Instrument
None - Indicates a reduced
performance condition.
None - Indicates a condition
that could cause damage to
the instrument or actuator.
None - Indicates a condition
that could reduce performance
or prevent the valve from
shutting tightly.
None - Indicates a condition
that could shorten service life
or lead to reduced
performance.
-Continued-
Instruction Manual
D103412X012
Recommended
Help
Action
Check instrument
The instrument has
feedback linkage
detected that the travel
and travel sensor.
sensor is outside its
normal range of
operation or that a
gross deviation exists
between set point and
actual travel. It has
switched to Pressure
Control and is no
longer using the travel
sensor to position the
valve.
Confirm proper
The Supply Pressure
air supply.
sensor on‐board has
detected an abnormally
high supply pressure.
Verify the proper
supply pressure and
that the alert is
properly set.
The Supply Pressure
sensor on‐board has
detected an abnormally
low supply pressure.
Verify the proper
supply pressure and
that the alert is
properly set.
Check instrument
The instrument
environment.
temperature has
exceeded the user
configured high
temperature limit.
Operation of the
instrument above the
rated temperature may
degrade instrument
components. This may
affect instrument
performance and/or
reduce the life of the
instrument.
The instrument
temperature has
dropped below the user
configured low
temperature limit.
Operation of the
instrument below the
rated temperature may
degrade instrument
components. This may
affect instrument
performance and/or
reduce the life of the
instrument.