Fisher FIELDVUE DVC6200f Instruction Manual page 26

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Installation
July 2013
Figure 2‐17. Modifications for Fisher GX Actuator; Air‐to‐Open Construction Only
PNEUMATIC
PORT
INSTALL
O‐RING
X0128
Air‐to‐Close GX Actuators
6. Using a 5 mm hex wrench, attach the feedback unit to the GX actuator mounting pad.
7. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
8. Install tubing between the actuator casing and the appropriate DVC6215 pneumatic output port.
9. If not already installed, install a vent in the port on the lower diaphragm casing.
Note
D
To convert to air-to-open, install an O‐ring between the feedback units pneumatic output and the actuator mounting pad.
Connect pneumatic tubing from the DVC6205f to the DVC6215. Refer to figure 2‐17.
D
To convert to air-to-close, remove the O‐ring between the feedback units pneumatic output and the actuator mounting pad.
Disconnect the pneumatic tubing from the DVC6205f to the DVC6215. Install tubing between the pneumatic output connection
of the DVC6205f to the pneumatic port on top of the actuator casing.
24
PNEUMATIC TUBING
FROM THE DVC6205f
Instruction Manual
D103412X012