Table 4‐40. Input Selector Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Update Event
UPDATE_EVT
UNACKNOWLEDGED
UPDATE_STATE
TIME_STAMP
STATIC_REVISION
RELATIVE_INDEX
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
In 5
IN_5
In 6
IN_6
In 7
IN_7
In 8
IN_8
Disable Analog Input 5
DISABLE_5
Disable Analog Input 6
DISABLE_6
Index
Block
RO / RW
Number
Mode
23
23.1
RW
N/A
23.2
RO
N/A
23.3
RO
N/A
23.4
RO
N/A
23.5
RO
N/A
24
24.1
RW
N/A
24.2
RO
N/A
24.3
RO
N/A
24.4
RO
N/A
24.5
RO
N/A
25
ALL
26
ALL
27
ALL
28
ALL
29
ALL
30
ALL
Initial
Range
Value
0=Undefined
1=Acknowledged
0
2=Unacknowledged
0=Undefined
1=Update Reported
0
2=Updated not
reported
0
0
0
0=Undefined
1=Acknowledged
0
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
0
3=Active reported
4=Active not
reported
0
0
0
Extended Parameters
BAD
Status
NC
constant
Value
0
BAD
NC
Status
constant
Value
0
BAD
Status
NC
constant
Value
BAD
Status
NC
constant
Value
0
BAD
Status
NC
constant
Value
0=Use
0
1=Disable
BAD
NC
Status
constant
0
Value
0=Use
0
1=Disable
-Continued-
Detailed Setup—ISEL Function Block
Description
Data Type: DS‐73
This alert is generated by any change to the static data.
Data Type: DS‐72
The block alarm is used for all configuration, hardware,
connection failure, or system problems in the block.
The cause of the alert is entered in the subcode field.
The first alert to become active will set the active
status in BLOCK_ERR. As soon as the Unreported status
is cleared by the alert reporting task, another block
alert may be reported without clearing the Active
status, if the subcode has changed.
Data Type: DS‐65
Input value and status.
Data Type: DS‐65
Input value and status.
Data Type: DS‐65
Input value and status.
Data Type: DS‐65
Input value and status.
Data Type: DS‐66
Enable/Disable for Input_5, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.
Data Type: DS‐66
Enable/Disable for Input_6, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.
July 2013