Table 4‐3. Resource Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
ROUT Timeout
SHED_ROUT
Fault State
FAULT_STATE
Set Fault State
SET_FSTATE
Clear Fault State
CLR_FSTATE
Maximum Notify
MAX_NOTIFY
Maximum Alerts Allow
LIM_NOTIFY
Confirm Time
CONFIRM_TIME
Index
RO /
Mode
Number
RW
27
RW
ALL
Positive
1=Clear
28
RO
N/A
2=Active
1=Off
29
RW
ALL
2=Set
1=Off
30
RW
ALL
2= Clear
31
RO
N/A
3
32
RW
ALL
0 to MAX_NOTIFY
> 0
33
RW
ALL
Set by FCS
-Continued-
Detailed Setup—Resource Block
Initial
Range
Value
Data Type: Unsigned32
Time duration (in 1/32 millisecond) at which to
give up on computer writes to function block
ROUT parameters. If this time is exceeded then
640000
the function block will change to a mode other
than ROUT based on the SHED_OPT parameter
setting. Shed from ROUT mode never happens
when SHED_ROUT is set to zero.
Data Type: Unsigned8
Forces output function blocks that are not Out
of Service to the fault state condition. While this
parameter is active the output function blocks
will go to an actual mode of Local Override (LO)
and will perform their fault state actions (see
Action On Fault Detection for the output blocks
1=Clear
on pages 118 and 194 of this section). This
parameter is used to test the fault state behavior
that normally occurs when there is a
communication problem between devices. This
parameter is changed by the SET_FSTATE and
CLR_FSTATE parameters so long as the feature
Fault State is selected (see Feature Selection
[index number 18] in this table).
Data Type: Unsigned8
Selecting Set changes the parameter
FAULT_STATE to Active. This is essentially a
"write only" parameter as it will always read OFF
1=Off
because it is defined as momentary. Writing a
value of OFF has no affect. To use this parameter
the feature Fault State must be selected (see
Features Selected on page 47).
Data Type: Unsigned8
Selecting Clear changes the parameter
FAULT_STATE to Clear and clears the output
function blocks of the FAULT_STATE if the field
condition, if any, has cleared. This is essentially a
1=Off
"write only" parameter as it will always read OFF
because it is defined as momentary. Writing a
value of OFF has no affect. To use this parameter
the feature Fault State must be selected (see
Features Selected on page 47.
Data Type: Unsigned8
The maximum number of alert reports that this
device can send without getting a confirmation.
3
To control alert flooding, the number can be set
lower by adjusting the LIM_NOTIFY parameter
value. For DVC6200f instruments, this value is
fixed at 3.
Data Type: Unsigned8
The number of alert reports that this device can
send without getting a confirmation up to the
MAX_NOTIFY
maximum permitted in the parameter
MAX_NOTIFY. If set to zero, then no alerts are
reported.
Data Type: Unsigned32
The time (in 1/32 millisecond) the device waits
640000
for confirmation of receipt of an alert report
before trying again.
July 2013
Description
57