Viewing Device Variables and Diagnostics
July 2013
Device Record
TB > Device Diagnostic > Device Record
Field Communicator
The following parameters are contained in the Device Record menu of the transducer block.
D Maximum Recorded Temperature—Maximum Recorded Temperature (TEMP_MAX [86.1]) shows the maximum
temperature the instrument has experienced since installation.
D Maximum Recorded Temperature Time—Maximum Recorded Temperature Time (TEMP_MAX_TIME [86.2]) shows
the date and time when the Temperature Maximum occurred.
D Minimum Recorded Temperature—Minimum Recorded Temperature (TEMP_MIN [86.3]) shows the minimum
temperature the instrument has experienced since installation.
D Minimum Recorded Temperature Time—Minimum Recorded Temperature Time (TEMP_MIN_TIME [86.4]) shows
the date and time when the Temperature Minimum occurred.
D Maximum Recorded Supply Pressure—Maximum Recorded Supply Pressure (SUPPLY_PRESS_MAX [86.5]) shows the
maximum supply pressure the instrument has experienced since installation.
D Maximum Recorded Supply Pressure Time—Maximum Recorded Supply Pressure Time (SUPP_PRESS_MAX_TIME
[86.6]) shows the date and time when the Supply Pressure Maximum occurred.
D Minimum Recorded Supply Pressure—Minimum Recorded Supply Pressure (SUPP_PRESS_MIN [86.7]) shows the
minimum supply pressure the instrument has experienced since installation.
D Minimum Recorded Supply Pressure Time—Minimum Recorded Supply Pressure Time (SUPP_PRESS_MIN_TIME
[86.8]) shows the date and time when the Supply Pressure Minimum occurred.
Stroking the Digital Valve Controller Output
TB > Device Diagnostic > Stroke Valve
Field Communicator
Stroke Valve is used to confirm proper valve operation. Follow the prompts on the Field Communicator display to
select from the following: Done, Ramp Open, Ramp Closed, Ramp to Target, Step to Target, and Stop.
D Done—Select this if you are done. All ramping is stopped when DONE is selected.
D Ramp Open—ramps the travel toward open at the rate of 1.0% per second of the ranged travel.
D Ramp Closed—ramps the travel toward closed at the rate of 1.0% per second of the ranged travel.
D Ramp to Target—ramps the travel to the specified target at the rate of 1.0% per second of the ranged travel.
D Step to Target—steps the travel to the specified target.
D Stop—stops the command.
228
Instruction Manual
D103412X012