Fisher FIELDVUE DVC6200f Instruction Manual page 139

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐32. PID Function Block System Parameters Definitions (Continued)
Label
PARAMETER_NAME
Update Event
UPDATE_EVT
UNACKNOWLEDGED
UPDATE_STATE
TIME_STAMP
STATIC_REVISION
RELATIVE_INDEX
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Alarm Summary
ALARM_SUM
CURRENT
UNACKNOWLEDGED
UNREPORTED
DISABLED
Acknowledge Option
ACK_OPTION
Alarm Hysteresis
ALARM_HYS
High High Priority
HI_HI_PRI
High High Limit
HI_HI_LIM
High Priority
HI_PRI
High Limit
HI_LIM
Low Priority
LO_PRI
Low Limit
LO_LIM
Low Low Priority
LO_LO_PRI
Index
RO /
Block
Number
RW
Mode
43
0=Undefined
43.1
RW
N/A
1=Acknowledged
2=
0=Undefined
43.2
RO
N/A
1=Update reported
2=Update not reported
43.3
RO
N/A
43.4
RO
N/A
43.5
RO
N/A
44
0=Undefined
44.1
RW
N/A
1=Acknowledged
2=
0=Undefined
1=Clear‐reported
2=Clear‐not reported
44.2
RO
N/A
3=Active reported
4=Active not reported
44.3
RO
N/A
44.4
RO
N/A
44.5
RO
N/A
45
1: High High Alarm
45.1
RO
ALL
2: High Alarm
45.2
RO
ALL
3: Low Low Alarm
4: Low Alarm
45.3
RO
ALL
5: Deviation High Alarm
6: Deviation Low Alarm
45.4
RW
ALL
7: Block Alarm
1: High High Alarm
2: High Alarm
3: Low Low Alarm
46
N/A
4: Low Alarm
5: Deviation High Alarm
6: Deviation Low Alarm
7: Block Alarm
47
ALL
0 to 50%
48
ALL
0 to 15
49
ALL
PV_SCALE, or +INF
50
ALL
0 to 15
51
ALL
PV_SCALE, or +INF
52
ALL
0 to 15
53
ALL
PV_SCALE, or -INF
54
ALL
0 to 15
Range
Initial Value
Unacknowledged
Unacknowledged
Dynamic
All bits: 0
0.50%
+INF
+INF
-INF
-Continued-
Detailed Setup—PID Function Block
Description
0
Data Type: DS‐73
This alert is generated by any changes to the static
0
data.
0
0
0
0
Data Type: DS‐72
The block alarm is used for all configuration,
hardware, connection failure, or system problems
in the block. The cause of the alarm will be set in
0
the subcode.
VALUE Data Type: Unsigned8
0
0
0
Data Type: DS‐74
Current alert status, unacknowledged states,
unreported states, and disabled states of the
alarms associated with the function block.
Data Type: Bit String
0=Disable
1=Enable
Used to set auto acknowledgment of alarms.
Data Type: Float
The amount the alarm value must return to within
the alarm limit before the associated active alarm
condition clears.
Data Type: Unsigned8
0
The priority of the HI HI Alarm.
Data Type: Float
The setting for the alarm limit used to detect the
HI HI alarm condition.
Data Type: Unsigned8
0
The priority of the HI alarm.
Data Type: Float
The setting for the alarm limit used to detect the
HI alarm condition.
Data Type: Unsigned8
0
The priority of the LO alarm.
Data Type: Float
The setting for the alarm limit used to detect the
LO alarm condition.
Data Type: Unsigned8
0
The priority of the LO LO alarm.
July 2013
137

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents