Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Update Event
UPDATE_EVT
UNACKNOWLEDGED
UPDATE_STATE
TIME_STAMP
STATIC_REVISION
RELATIVE_INDEX
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Transducer Directory
TRANSDUCER_DIRECTORY
Transducer Type
TRANSDUCER_TYPE
Transducer Error
XD_ERROR or TDC_ERROR
Collection Directory
COLLECTION_DIRECTORY
FINAL_VALUE
Setpoint Status
STATUS
Setpoint
VALUE
Setpoint Range
FINAL_VALUE_RANGE
EU_100
EU_0
UNITS_INDEX
DECIMAL
88
Index
RO /
Mode
Number
RW
7
0=Undefined
1=Acknowledged
7.1
RW
ALL
2=Unacknowledged
0=Undefined
1=Updated reported
7.2
RO
N/A
2=Update Not reported
7.3
RO
N/A
7.4
RO
N/A
7.5
RO
N/A
8
0=Undefined
1=Acknowledged
8.1
RW
ALL
2=Unacknowledged
0=Undefined
1=Clear-reported
8.2
RO
N/A
2=Clear-not reported
3=Active-reported
4=Active-not reported
8.3
RO
N/A
Subcode: Bit Number in
8.4
RO
N/A
BLOCK_ERR
Value of parameter at
alarm time for a single
8.5
RO
N/A
alarm, 0 for multiple
alarms
9
RO
N/A
1,1
10
RO
106
Valid Numbers: 0 = No
11
RO
Error
12
RO
1,1,1,1,1
13
MAN
13.1
RW
OOS
MAN
13.2
RW
-25 to 125
OOS
14
14.1
RO
N/A
100
14.2
RO
N/A
0
14.3
RO
N/A
PERCENT
14.4
RO
N/A
2
Range
Initial Value
0
0
0
0
0
0
0
0
0
0
1,1
106
0
1,1,1,1,1
N/A
N/A
100
0
1342
2
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
NONE
Data Type: DS‐73
N/A
Alert generated by change to static
data.
N/A
N/A
N/A
NONE
N/A
Data Type: DS‐72
Used to report the BLOCK_ERR
N/A
alarm to the host system
N/A
N/A
Data Type: Array [2] of Unit16
N/A
Not used
Data Type: Uint16
N/A
Identifies the type of the transducer.
Data Type: Uint8
N/A
Error code for the transducer block.
Data Type: Array [5] of Unit32
N/A
Not used
Data Type: DS‐65
In Travel Control: Setpoint for valve
travel in %, prior to characterization.
NONE
In Pressure Control: Setpoint for
implied valve travel as % or pressure
range, prior to characterization.
FINAL_VALUE is not updated unless
the AO block is selected in
FEATURE_SELECT. For example,
NONE
FINAL_VALUE still has last value
written by AO channel 1 when DO is
in control.
Data Type: DS‐68
High and Low range limit values,
N/A
engineering units code, and number
N/A
of digits to the right of the decimal
place to be used to display the Final
N/A
Value.
N/A