Fisher FIELDVUE DVC6200f Instruction Manual page 107

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Travel Open Alert Point
TVL_OPEN_ALRT_PT
Travel Open Deadband
TVL_OPEN_DB
Travel Closed Alert Point
TVL_CLOSED_ALRT_PT
Travel Closed Deadband
TVL_CLOSED_DB
Travel Lo Lo Alert Point
TVL_LO_LO_ALRT_PT
Travel Lo Lo Deadband
TVL_LO_LO_DB
Travel Lo Alert Point
TVL_LO_ALRT_PT
Travel Lo Deadband
TVL_LO_DB
Travel Hi Alert Point
TVL_HI_ALRT_PT
Travel Hi Deadband
TVL_HI_DB
Travel Hi Hi Alert Point
TVL_HI_HI_ALRT_PT
Travel Hi Hi Deadband
TVL_HI_HI_DB
Index
RO /
Mode
Number
RW
77.8
RW
ALL
-25% to 125%
> = 0%, < =100%
77.9
RW
ALL
77.10
RW
ALL
-25% to 125%
> = 0%, < = 100%
77.11
RW
ALL
77.12
RW
ALL
-25% to 125%
> = 0%, < = 100%
77.13
RW
ALL
77.14
RW
ALL
-25% to 125%
> = 0%, < = 100%
77.15
RW
ALL
77.16
RW
ALL
-25% to 125%
> = 0%, < = 100%
77.17
RW
ALL
77.18
RW
ALL
-25% to 125%
> = 0%, < = 100%
77.19
RW
ALL
Range
Initial Value
99.5%
1%
0.5%
1%
-25%
5%
-25%
5%
125%
5%
125%
5%
-Continued-
Detailed Setup—Transducer Block
Protect
Description
Category
Data Type: Float
Alert when valve is open. Control DI
SETUP
channel 24 regardless of alert enable
state.
Data Type: Float
SETUP
Deadband
Data Type: Float
Alerts when valve closed. Controls DI
SETUP
channel 25 regardless of alert enable
state.
Data Type: Float
SETUP
Deadband
Data Type: Float
Alert when valve position is less than
SETUP
alert point. Controls DI channels 26
& 30 regardless of alert enable state.
Data Type: Float
SETUP
Deadband
Data Type: Float
Alert when valve position is less than
SETUP
alert point. Controls DI channels 27
& 31 regardless of alert enable state.
Data Type: Float
SETUP
Deadband
Data Type: Float
Alert when valve position is less than
SETUP
alert point. Controls DI channels 28
& 32 regardless of alert enable state.
Data Type: Float
SETUP
Deadband
Data Type: Float
Alert when valve position is less than
SETUP
alert point. Controls DI channels 29
& 33 regardless of alert enable state.
Data Type: Float
SETUP
Deadband
July 2013
105

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents