Fisher FIELDVUE DVC6200f Instruction Manual page 208

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—DI Function Block
July 2013
To use simulate, first install the simulate jumper in the terminal box, then set Simulate_D enable/disable to enabled,
then enter the desired values for Simulate Value and Status.
When SIMULATE_D [9] is enabled, the Simulate Active bit of the BLOCK_ERR [6] parameter is set (refer to the Block
Errors description). When the simulate jumper is installed, the Simulate Jumper bit of the transducer block parameter
SELFTEST_STATUS [78] is set.
Application Information
Figure 4‐32 compares the operation of a standard discrete input to a proximity discrete input. With the standard
discrete input, the discrete input changes state when the valve position passes a configurable trip point. This can be
used to indicate if the valve position is above or below the trip point.
Figure 4‐32. Proximity Discrete Input Compared to a Standard Discrete Input
STANDARD DISCRETE INPUT
PROXIMITY DISCRETE INPUT
Configurable
Band
With the proximity discrete input a configurable band can be established about a central point. Whenever the valve
position enters this configurable band, the discrete input changes state. A proximity discrete input is useful for
applications which require knowing the location of the valve when the valve is not near 0% or 100%.
DI Function Block Parameter List (table 4‐81)
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shaded Index Number indicates sub‐parameter
206
DISCRETE
1
INPUT VALUE
0
DISCRETE
0
INPUT VALUE
1
0
Instruction Manual
D103412X012

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents