Fisher FIELDVUE DVC6200f Instruction Manual page 181

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐57. Analog Input Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Alarm Summary
ALARM_SUM
CURRENT
UNACKNOWLEDGED
UNREPORTED
DISABLED
Acknowledge Option
ACK_OPTION
Alarm Hysteresis
ALARM_HYS
High High Priority
HI_HI_PRI
High High Limit
HI_HI_LIM
High Priority
HI_PRI
Hi Limit
HI_LIM
Low Priority
LO_PRI
Low Limit
LO_LIM
Low Low Priority
LO_LO_PRI
Low Low Limit
LO_LO_LIM
High High Alarm
HI_HI_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
High Alarm
HI_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Low Alarm
LO_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Index
RO /
Write Block
Number
RW
Mode
22
22.1
RO
ALL
22.2
RO
ALL
22.3
RO
ALL
22.4
RW
ALL
23
ALL
24
ALL
25
ALL
26
ALL
27
ALL
28
ALL
29
ALL
30
ALL
31
ALL
32
ALL
33
33.1
RW
33.2
RO
33.3
RO
N/A
33.4
RO
33.5
RO
34
34.1
RW
34.2
RO
34.3
RO
N/A
34.4
RO
34.5
RO
35
35.1
RW
35.2
RO
35.3
RO
N/A
35.4
RO
35.5
RO
Initial
Range
Value
0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
All bits: 0
7: Block alarm
0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
All bits: 0
3: Lo Lo Alarm
4: Lo Alarm
7: Block alarm
0 - 50%
0.50%
0 to 15
0
OUT_SCALE
0
0 to 15
0
OUT_SCALE
0
0 to 15
0
OUT_SCALE
0
0 to 15
0
OUT_SCALE
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-Continued-
Detailed Setup—AI Function Block
Description
Data Type: DS‐74 Current alert status,
unacknowledged states, unreported states, and
disabled states of the alarms associated with the
function block.
0=clear
0=acknowledged
0=reported
0=enabled
Data Type: Bit String
0
Disable
=
1
Enable
=
Selection of whether alarms associated with the
block will be automatically acknowledged.
Data Type: Float
Hysteresis on alarms.
Data Type: Unsigned8
The priority of the hi hi alarm.
Data Type: Float
Value of analog input which will generate an alarm.
Data Type: Unsigned8
The priority of the high alarm.
Data Type: Float
Value of analog input which will generate an alarm.
Data Type: Unsigned8
The priority of the low alarm.
Data Type: Float
Value of analog input which will generate an alarm.
Data Type: Unsigned8
The priority of the low low alarm.
Data Type: Float
Value of analog input which will generate an alarm.
Data Type: DS‐71
The status of the hi hi alarm and its associated time
stamp.
Data Type: DS‐71
The status of the hi alarm and its associated time
stamp.
Data Type: DS‐71
The status of the lo alarm and its associated time
stamp.
July 2013