Table 4‐32. PID Function Block System Parameters Definitions (Continued)
Label
PARAMETER_NAME
Bypass
BYPASS
Cascade Input
CAS_IN
Setpoint Rate Down
SP_RATE_DN
Setpoint Rate UP
SP_RATE_UP
Setpoint High Limit
SP_HI_LIM
Setpoint Low Limit
SP_LO_LIM
Gain
GAIN
Reset
RESET
Balance Time
BAL_TIME
Rate
RATE
Back Calculation Input
BKCAL_IN
Output High Limit
OUT_HI_LIM
Output Low Limit
OUT_LO_LIM
Back Calculation Hysteresis
BKCAL_HYS
Back Calculation Output
BKCAL_OUT
Remote Cascade Input
RCAS_IN
Index
RO /
Block
Number
RW
Mode
MAN
1=Off
17
OOS
2=On
Status
18
ALL
Value
19
ALL
Positive
20
ALL
Positive
PV Scale +/- 10%, must be
21
ALL
greater than SP_LO_LIM
PV Scale
22
ALL
+/- 10%, must be less than
SP_HI_LIM
23
ALL
greater than 0
24
ALL
Positive
25
ALL
Positive
26
ALL
Positive
Status
27
ALL
Value
28
ALL
OUT_SCALE +/- 10%
29
ALL
OUT_SCALE +/- 10%
30
ALL
0 to 50%
31
RO
N/A
Status
32
ALL
Value
Detailed Setup—PID Function Block
Range
Initial Value
0=undefined
BAD
NC:
const
0
+ INF
+ INF
100
0
1
+ INF
0
0
BAD:
NC:
const
0
100
0
0.50%
Dynamic
BAD:
NoCom:
NoVal:
const
0 Trk
-Continued-
Description
Data Type: Enum
Used to override the calculation of the block.
When enabled, the SP is sent directly to the
output.
Data Type: DS‐65
The setpoint value from another block.
Data Type: Float
Ramp rate for downward SP changes. When the
ramp rate is set to zero, the SP is used
immediately. PV per second
Data Type: Float
Ramp rate for upward SP changes. When the ramp
rate is set to zero, the SP is used immediately. PV
per second
Data Type: Float
The highest SP value allowed.
Data Type: Float
The lowest SP value allowed.
Data Type: Float
The proportional gain value.
Data Type: Float
The integral action time constant. Seconds per
repeat
Data Type: Float
The specified time, in seconds, for the internal
working value of bias to return to the operator set
bias. Also used to specify the time constant at
which the integral term will move to obtain
balance when the output is limited and the mode is
AUTO, CAS, or RCAS.
Data Type: Float
The derivative action time constant, in seconds.
Data Type: DS‐65
The analog input value and status from another
block's BKCAL_OUT output that is used for
backward output tracking for bumpless transfer
and to pass limit status.
Data Type: Float
Limits the maximum output value for modes other
than manual.
Data Type: Float
Limits the minimum output value for modes other
than manual.
Data Type: Float
The amount the output value must change away
from the its output limit before limit status is
turned off.
Data Type: DS‐65
The value and status required by the BKCAL_IN
input of another block to prevent reset windup and
to provide bumpless transfer of closed loop
control.
Data Type: DS‐65
Target setpoint and status that is provided by a
supervisory host. Used when mode is RCAS.
July 2013