Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
INST_ALERTS_CONFIG
Shutdown Trigger
SHUTDOWN_TRIGGER
Shutdown Recovery
SHUTDOWN_RECOVERY
Output Blk Timeout
OUTPUT_BLK_TIMEOUT
Drive Current Alert Point
DRIVE_CURRENT_ALRT_PT
Drive Current Alert Time
DRIVE_CURRENT_TIME
Temperature Hi Alert Point
TEMP_HI_ALRT_PT
Temperature Lo Alert Point
TEMP_LO_ALRT_PT
Supply Pressure Hi Alert Point
SUP_PRES_HI_ALRT_PT
Supply Pressure Lo Alert Point
SUP_PRES_LO_ALRT_PT
INST_ALERTS_CONFIG2
Travel Deviation Alert Point
TVL_DEV_ALRT_PT
Travel Deviation Time
TVL_DEV_TIME
Travel Deviation Deadband
TVL_DEV_DB
Travel Accumulator Alert Point
TVL_ACCUM_ALRT_PT
Travel Accumulator Deadband
TVL_ACCUM_DB
Cycle Count Alert Point
CYCLE_COUNT_ALRT_PT
Cycle Count Deadband
CYCLE_COUNT_DB
104
Index
RO /
Mode
Number
RW
76
0: Drive Current
1: Program Memory
2: Static Memory
3: Processor or I/O
Processor
76.1
RW
ALL
4: Travel Sensor
5: Port A Pressure Sensor
6: Output Block Timeout
7-31: (Reserved)
0: (reserved)
1: Program Memory
2: Static Memory
3: Processor or I/O
76.2
RW
ALL
Processor
4: Travel Sensor
5: Port A Pressure Sensor
6: Output Block Timeout
7-31: (Reserved)
Time > = 0, < = 800
76.3
RW
ALL
seconds
> = 5, < = 100
76.4
RW
ALL
= 0.25, < = 120 seconds
76.5
RW
ALL
76.6
RW
ALL
> -76 F, < 257 F
76.7
RW
ALL
> -76 F, < 257 F
> = 0, < = 150
76.8
RW
ALL
> = 0, < = 150
76.9
RW
ALL
77
> 0%, <= 125%
77.1
RW
ALL
> = 0, < = 120 seconds
77.2
RW
ALL
> = 0%, < = 100%
77.3
RW
ALL
> = 0
77.4
RW
ALL
77.5
RW
ALL
0 - 100%
> = 0
77.6
RW
ALL
77.7
RW
ALL
0 - 100%
Range
Initial Value
All bits: 0
All bits: 0
600 sec
25%
5 sec
186 deg F
-63 deg F
145 psig
15 psig
5%
10 sec
2%
1,000,000
1%
1,000,000
1%
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
Data Type: Bit String (4 byte)
0=attempt control,
1=fail to zero drive e.g. OOS mode
SETUP
Action on specific instrument alerts:
Data Type: Bit String (4 byte)
0=Auto
SETUP
1=Manual
Recovery action after a shutdown
trigger "fail to zero drive" above,
Data Type: Float
The maximum time between
SETUP
updates from the AO or DO block to
the transducer block setpoint.
Data Type: Float
(percent different) drive signal not
SETUP
reaching I/P accurately.
Data Type: Float
SETUP
(percent different) drive signal not
reaching I/P accurately.
Data Type: Float
SETUP
Temperature HI Limits
Data Type: Float
SETUP
Temperature LO Limits
Data Type: Float
SETUP
Maximum supply pressure
Data Type: Float
SETUP
Minimum supply pressure
Data Type: Float
Alerts when difference between sp
SETUP
and pv is too large for too long.
SETUP
Data Type: Float
SETUP
Data Type: Float
Data Type: Uint32
Alerts when accumulated travel is
SETUP
too much
Data Type: Float
SETUP
Deadband
Alerts when number of cycles is too
SETUP
large.
Data Type: Float
SETUP
Deadband