Fisher FIELDVUE DVC6200f Instruction Manual page 106

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
INST_ALERTS_CONFIG
Shutdown Trigger
SHUTDOWN_TRIGGER
Shutdown Recovery
SHUTDOWN_RECOVERY
Output Blk Timeout
OUTPUT_BLK_TIMEOUT
Drive Current Alert Point
DRIVE_CURRENT_ALRT_PT
Drive Current Alert Time
DRIVE_CURRENT_TIME
Temperature Hi Alert Point
TEMP_HI_ALRT_PT
Temperature Lo Alert Point
TEMP_LO_ALRT_PT
Supply Pressure Hi Alert Point
SUP_PRES_HI_ALRT_PT
Supply Pressure Lo Alert Point
SUP_PRES_LO_ALRT_PT
INST_ALERTS_CONFIG2
Travel Deviation Alert Point
TVL_DEV_ALRT_PT
Travel Deviation Time
TVL_DEV_TIME
Travel Deviation Deadband
TVL_DEV_DB
Travel Accumulator Alert Point
TVL_ACCUM_ALRT_PT
Travel Accumulator Deadband
TVL_ACCUM_DB
Cycle Count Alert Point
CYCLE_COUNT_ALRT_PT
Cycle Count Deadband
CYCLE_COUNT_DB
104
Index
RO /
Mode
Number
RW
76
0: Drive Current
1: Program Memory
2: Static Memory
3: Processor or I/O
Processor
76.1
RW
ALL
4: Travel Sensor
5: Port A Pressure Sensor
6: Output Block Timeout
7-31: (Reserved)
0: (reserved)
1: Program Memory
2: Static Memory
3: Processor or I/O
76.2
RW
ALL
Processor
4: Travel Sensor
5: Port A Pressure Sensor
6: Output Block Timeout
7-31: (Reserved)
Time > = 0, < = 800
76.3
RW
ALL
seconds
> = 5, < = 100
76.4
RW
ALL
= 0.25, < = 120 seconds
76.5
RW
ALL
76.6
RW
ALL
> -76 F, < 257 F
76.7
RW
ALL
> -76 F, < 257 F
> = 0, < = 150
76.8
RW
ALL
> = 0, < = 150
76.9
RW
ALL
77
> 0%, <= 125%
77.1
RW
ALL
> = 0, < = 120 seconds
77.2
RW
ALL
> = 0%, < = 100%
77.3
RW
ALL
> = 0
77.4
RW
ALL
77.5
RW
ALL
0 - 100%
> = 0
77.6
RW
ALL
77.7
RW
ALL
0 - 100%
Range
Initial Value
All bits: 0
All bits: 0
600 sec
25%
5 sec
186 deg F
-63 deg F
145 psig
15 psig
5%
10 sec
2%
1,000,000
1%
1,000,000
1%
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
Data Type: Bit String (4 byte)
0=attempt control,
1=fail to zero drive e.g. OOS mode
SETUP
Action on specific instrument alerts:
Data Type: Bit String (4 byte)
0=Auto
SETUP
1=Manual
Recovery action after a shutdown
trigger "fail to zero drive" above,
Data Type: Float
The maximum time between
SETUP
updates from the AO or DO block to
the transducer block setpoint.
Data Type: Float
(percent different) drive signal not
SETUP
reaching I/P accurately.
Data Type: Float
SETUP
(percent different) drive signal not
reaching I/P accurately.
Data Type: Float
SETUP
Temperature HI Limits
Data Type: Float
SETUP
Temperature LO Limits
Data Type: Float
SETUP
Maximum supply pressure
Data Type: Float
SETUP
Minimum supply pressure
Data Type: Float
Alerts when difference between sp
SETUP
and pv is too large for too long.
SETUP
Data Type: Float
SETUP
Data Type: Float
Data Type: Uint32
Alerts when accumulated travel is
SETUP
too much
Data Type: Float
SETUP
Deadband
Alerts when number of cycles is too
SETUP
large.
Data Type: Float
SETUP
Deadband