remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
D Static Memory Alert—This alert is active if a failure occurs in the FRAM memory where the static parameters are
stored.
D Static Memory Alert Enable—When enabled Static Memory Alert Enable activates the Static Memory Alert.
D Static Memory Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the Static Memory Alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
D Static Memory Manual Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when the condition that caused Static Memory Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
D Processor Alert—This alert is active if a failure occurs in the main processor.
D Processor Alert Enable—When enabled Processor Alert Enable activates the Processor Alert.
D I/O Processor Alert—This alert is active if a failure occurs in the I/O processor.
D I/O Processor Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the I/O Processor Alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
D I/O Processor Man Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or disabling
Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target mode when
the condition that caused I/O Processor Shutdown clears. If not enabled, the transducer block will remain Out of
Service until power is removed and restored or the user changes the transducer block target mode to Manual or
Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or
until the shutdown trigger is disabled.
Configuration Alerts
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts
Field Communicator
Output Block Timeout
D Output Block Timeout Alert—This alert is active if the analog or discrete output block has not executed for longer
than the configured timeout.
D Output Block Timeout Alert Enable—When enabled Output Block Timeout Alert Enable activates the Output Block
Timeout Alert.
D Output Block Timeout Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or
disabling Self Test Shutdown. When enabled, and the Output Block Timeout Alert is active, the transducer Actual
Detailed Setup—Transducer Block
July 2013
71