Table 4‐40. Input Selector Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
High Alarm
HI_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Low Alarm
LO_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Low Low Alarm
LO_LO_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Output Discrete
OUT_D
Alarm Select
ALM_SEL
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Index
Block
RO / RW
Number
Mode
46
46.1
RW
N/A
46.2
RO
N/A
46.3
RO
N/A
46.4
RO
N/A
46.5
RO
N/A
47
47.1
RW
N/A
47.2
RO
N/A
47.3
RO
N/A
47.4
RO
N/A
47.5
RO
N/A
48
48.1
RW
N/A
48.2
RO
N/A
48.3
RO
N/A
48.4
RO
N/A
48.5
RO
N/A
MAN
49
OOS
50
ALL
Initial
Range
Value
0=Undefined
1=Acknowledged
0
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
0
3=Active reported
4=Active not
reported
0
0
0
0=Undefined
1=Acknowledged
0
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
0
3=Active reported
4=Active not
reported
0
0
0
0=Undefined
1=Acknowledged
0
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
0
3=Active reported
4=Active not
reported
0
0
0
Status
Value
0, 1
Status
1: Hi Hi
2: Hi
All bits:0
3: Lo Lo
4: Lo
Detailed Setup—ISEL Function Block
Description
Data Type: DS‐71
The high alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of the
alarm.
Data Type: DS‐71
The low alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of the
alarm.
Data Type: DS‐71
The low low alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of the
alarm.
Data Type: DS‐66
Discrete output to indicate a selected alarm value
Data Type: Bit String
Used to select the process alarm conditions that will
cause the OUT_D parameter to be set.