Function Block - Fisher FIELDVUE DVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—PID Function Block
July 2013
PID Function Block
Overview
The PID function block (figure 4‐9) combines all of the necessary logic to perform proportional/integral/derivative
(PID) control. The block supports mode control, signal scaling and limiting, feedforward control, override tracking,
alarm limit detection, and signal status propagation.
Figure 4‐9. Proportional+Integral+Derivative (PID) Function Block
BKCAL
IN
CAS
IN
FF
VAL
IN
TRK
IN
D
TRK
VAL
BKCAL_IN
THE ANALOG INPUT VALUE AND STATUS FROM ANOTHER BLOCK'S BKCAL
=
_OUT OUTPUT THAT IS USED FOR BACKWARD OUTPUT TRACKING FOR BUMPLESS
TRANSFER AND TO PASS LIMIT STATUS.
CAS_IN
=
THE REMOTE SETPOINT VALUE FROM ANOTHER FUNCTION BLOCK.
FF_VAL
THE FEEDFORWARD CONTROL INPUT VALUE AND STATUS.
=
IN
THE CONNECTION FOR THE PROCESS VARIABLEFROM ANOTHER FUNCTION BLOCK.
=
TRK_IN_D
=
INITIATES THE EXTERNAL TRACKING FUNCTION.
TRK_VAL
THE VALUE AFTER SCALING APPLIED TO OUT IN LOCAL OVERRIDE MODE.
=
BKCAL_OUT
THE VALUE AND STATUS REQUIRED BY THE BKCAL_IN INPUT OF ANOTHER
=
FUNCTION BLOCK TO PREVENT RESET WINDUP AND TO PROVIDE BUMPLESS TRANSFER
TO CLOSED LOOP CONTROL.
OUT
=
THE BLOCK OUTPUT AND STATUS.
B2720
The block supports two forms of the PID equation: Standard and Series. You can choose the appropriate equation
using the MATHFORM [70] parameter. The Standard ISA PID equation is the default selection.
Standard Out + GAIN
ex
Series Out + GAIN
ex
where
GAIN:
proportional gain value
τ
:
integral action time constant (RESET parameter) in seconds
r
s:
laplace operator
τ
:
derivative action time constant (RATE parameter)
d
126
BKCAL OUT
OUT
PID
t
s
1
1 )
)
d
t
s ) 1
T
t
s ) 1
r
d
t
s ) 1
1 ) 1 t
s )
d
T
t
s ) 1
r
d
)
)F
Instruction Manual
D103412X012

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents