Detailed Setup—AI Function Block
July 2013
Table 4‐57. Analog Input Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Grant Deny
GRANT_DENY
GRANT
DENY
I/O Options
IO_OPTS
Status Options
STATUS_OPTS
AI Channel
CHANNEL
Linearization Type
L_TYPE
Low Cutoff
LOW_CUT
Process Value Filter Time
PV_FTIME
Field Value
FIELD_VAL
Updated Event
UPDATE_EVT
UNACKNOWLEDGED
UPDATE_STATE
TIME_STAMP
STATIC_REVISION
RELATIVE_INDEX
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
178
Index
RO /
Write Block
Number
RW
Mode
12
12.1
ALL
12.2
ALL
13
OOS
14
OOS
15
OOS
16
OOS, MAN
17
ALL
18
ALL
19
RO
20
20.1
RW
N/A
20.2
RO
N/A
20.3
RO
N/A
20.4
RO
N/A
20.5
RO
N/A
21
21.1
RW
21.2
RO
21.3
RO
21.4
RO
21.5
RO
Initial
Range
Value
Valid Bits
All bits: 0
0: Program
1: Tune
2: Alarm
All bits: 0
3: Local
10: Low cutoff
All bits: 0
3: Propagate Failure
forward
6: Uncertain if Limited
All bits: 0
7: Bad if Limited
8: Uncertain in Man
Mode
See table 4‐54
0: Undefined
0: Undefined
1: Direct
0: Undefined
2: Indirect
3: Ind. Sqr. Root
Positive
0
Positive
0
0
0
Undefined
=
1
Acknowledged
0
Undefined
=
=
2
Unacknowledged
=
0
Undefined
=
1
Update reported
0
Undefined
=
=
2
Update not reported
=
0
0
0
0
Undefined
=
1
Acknowledged
=
2
Unacknowledged
=
0
Undefined
=
1
Clear‐reported
=
2
Clear‐not reported
=
3
Active‐reported
=
4
Active‐not reported
=
-Continued-
Instruction Manual
Description
Data Type: DS‐70
Options for controlling access of host computer and
local control panels to operating, tuning, and alarm
parameters of the block.
GRANT: 0=N/A, 1=granted
DENY: 0=N/A, 1=denied
Data Type: Bit String
0=Disable
1=Enable
User options for Output Control.
Data Type: Bit String
0=Disable
1=Enable
User options for Status
Data Type: Unsigned16
Used to select the type of threshold that is used to
set the output.
Data Type: Enum
Linearization type. Determines whether the field
value is used directly (Direct), is converted linearly
(Indirect), or is converted with the square root
(Indirect Square Root). The OUT_SCALE is normally
the same as the transducer, but if L_TYPE is set to
Indirect or Ind Sqr Root, OUT_SCALE determines the
conversion from FIELD_VAL to the output.
Data Type: Float
If calculated output is below this value the output is
0.
Data Type: Float
Time constant of first order filter on PV, in seconds.
Data Type: DS‐65
Value of the field device analog input, with a status
reflecting the Transducer condition.
Data Type: DS‐73
This alarm is generated whenever a static parameter
is changed.
Data Type: DS‐72
The block alarm is used for all configuration,
hardware, connection failure or system problems in
the block. The cause of the alert is entered in the
subcode field.