Fisher FIELDVUE DVC6200f Instruction Manual page 100

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Advise Active
ADVISE_ACTIVE
Failed Enable
FAILED_ENABLE
Maintenance Enable
MAINT_ENABLE
Advise Enable
ADVISE_ENABLE
Failed Suppress
FAILED_MASK
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
98
Index
RO /
Mode
Number
RW
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
9: Supply Pressure
(1)
61
RO
N/A
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
Same as for
62
RW
ALL
FAILED_ACTIVE above
Same as for
63
RW
ALL
MAINT_ACTIVE above
Same as for
64
RW
ALL
ADVISE_ENABLE above
Same as for
65
RW
ALL
FAILED_ACTIVE above
Range
Initial Value
All bits: 0
Enabled Bits:
0: Drive Current
2: Processor
Impaired
4: Blocks Set to
Default
5: Travel Sensor
15: Performance
Critical
18: Shutdown
Alert
Enabled Bits:
1: Drive Signal
3: Output Block
Timeout
6: Outlet Pressure
Sensor
9: Supply Pressure
11: Travel
Deviation
13: Travel
Accumulator
14: Cycle Counter
16: Performance
Reduced
Enabled Bits:
8: Temperature
Sensor
9: Supply Pressure
Sensor
10: Temperature
Limit
12: Travel Limit
All bits: 0
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
Data Type: Bit String (4 byte)
0=inactive
N/A
1=active
Advise Alert Status
Data Type: Bit String (4 byte)
0=disable
1=enable
ALL
Failed alert enable. Enable allows
detection of alert. All alerts can be
disabled.
Data Type: Bit String (4 byte)
0=disable
1=enable
ALL
Maintenance alert enable. Enable
allows detection of alert. All alerts
can be disabled.
Data Type: Bit String (4 byte)
0=disable
1=enable
ALL
Advise alert enable. Enable allows
detection of alert. All alerts can be
disabled.
Data Type: Bit String (4 byte)
0=disable
1=enable
Failed alert mask.
MASK controls whether an alert is
reported. If alert is enabled the alert
ALL
condition is evaluated and the
ACTIVE parameter is updated to
reflect if alert is active or not. If the
bit is set reporting is suppressed.
Default is all bits cleared.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents